The Lumberg Automation 934692002 0980 ESL 802 Lion-R is an active 8 port 5 pin M12 distribution block, with 16 digital outputs. Has LEDs to indicate the current status and two 7/8" power supply ports. It is a Profinet device, designed to operate under more extreme conditions and create secure communication of data. Rated IP 67.
Features
- Galvanic isolation between sensors/actuators and Profinet
- Less time required to find a fault
- "Fail safe" function promotes reliability & switches the module off if a fault is found
- Support for RT and IRT in real time standards
- Multiple M12 connections reduce time and cost, while making it easy to expand
- Integrated 10/100 Mbs dual port switch for line topologies
- 7/8" power supply & M12 ports support T distributors
- Vibration resistant
- Overall mechanical stability and functional reliability
- PNO certification
TECHNICAL DATA
- Protection Class- IP 67
- Operating Temperature Range- -10 C to 60 C (14 F to 140 F)
- Housing Material- Diecast Zinc
- Dimensions- 261.4mm Length x 59.6mm Width x 17.6mm Height (10.3" x 2.35" x 0.7")
BUS SYSTEM
- Transmission Rate- 10/100 Mbs
- Address Range- 0-255 (default address 0)
ACTUATOR POWER SUPPLY UL
- Rated Output Current- 24 VDC
- Voltage Range- 19 - 30 VDC
- Reverse Polarity Protection- Yes/Antiparallel diode
- Indicator- LED green
OUTPUTS
- Rated Output Current- 1.6 A per channel
- Short Circuit Proof- Yes
- Max. Current Carrying Capacity- 9 A per module
- Overload Proof- Yes
- Number of Digital Channels- 16
- Channel Type N.O.- P-switching
- Status Indicator- LED white per channel
- Diagnostic Indicator- LED red per port
- Galvanic Isolation from Electronics- Yes
- Approvals- UL, CSA
Diagnostic Information
|
LED
|
Indication
|
Condition
|
Us
|
Green
|
Logic/sensor power supply
|
UL
|
Green
|
Actuator power supply
|
1...8 A
|
Yellow
|
Channel status
|
1...8 DIA A
|
Red
|
Periphery error
|
1...8 B
|
Yellow
|
Channel status
|
1...8 DIA B
|
Red
|
Periphery error
|
P1 Lnk/Act
|
Green
Yellow flashing Off
|
Connection to a Profinet device
I/O device exchanging data No connection to any devices
|
P2 Lnk/Act
|
Green
Yellow flashing Off
|
Connection to an Profinet device
I/O device exchanging data No connection to any devices
|
BF
|
Red
Off
|
Bus error, no data exchange with I/O controller
No error
|
DIA
|
Red
Red flashing Off
|
Common indicator for periphery errors
Firmware update No error
|
Lumberg Automation Profinet M12 Distribution Block
|
|
|
|
|
|
|