The Lumberg Automation 934691001 0980 ESL 811 Lion-R is an active 8 port 5 pin M12 distribution block, with 16 digital inputs. Has rotary switches for setting addresses, with two 7/8" power supply ports. It is made to operate under more extreme conditions and create secure communication of data. It can be used to connect sensors and actuators to Ethernet/IP networks. Rated IP 67.
Features
- Galvanic isolation between sensors, actuators and Ethernet/IP
- Less time required to find a fault
- "Fail safe" function promotes reliability & switches the module off if a fault is found
- Integrated 10/100 Mbs dual port switch for line and ring topologies
- Color coded connectors
- Rotary switches or webserver set up IP addresses
- 7/8" power supply & M12 ports support T distributors
- Vibration resistant
- Overall mechanical stability and functional reliability
Technical Data
- Protection Class- IP 67
- Operating Temperature Range- -10 C to 60 C (14 F to 140 F)
- Housing Material- Diecast Zinc
- Dimensions- 261.4mm Length x 59.6mm Width x 17.6mm Height (10.3" x 2.35" x 0.7")
Bus System
- Transmission Rate- 10/100 Mbs
- Address Range- 0-255 (default address 0)
Inputs
- Rated Voltage- 24 VDC
- Sensor Type- PNP (source)
- Power Consumption of Sensor- Max. 200 mA
- Reverse Polarity Protection- Yes
- Short Circuit Proof- Yes
- Number of Digital Channels- 16
- Status Indicator- LED white per channel
- Diagnostic Indicator- LED red per port
- Approvals- UL, CSA
Diagnostic Information
|
LED
|
Indication
|
Condition
|
1...8 A
|
White
|
Channel status
|
1...8 DIA A
|
Red
|
Periphery error
|
1...8 B
|
White
|
Channel status
|
1...8 DIA B
|
Red
|
Periphery error
|
P1 Lnk/Act
|
Green
Yellow flashing Off
|
Connection to an Ethernet device
I/O device exchanging data No connection to any devices
|
P2 Lnk/Act
|
Green
Green flashing Off
|
Connection to an Ethernet device
I/O device exchanging data No connection to any devices
|
MS (module status)
|
Green
Green flashing Red/Green flashing Red flashing Off
|
Device ready
Wrong configuration Self test running Firmware update Device is off
|
NS (network status)
|
Green flashing
Green Red flashing Red Red/Green flashing Off
|
IP address is available
Connection to master is available At least one connection timed out IP address being used by another device Self test running Device is off/has no IP address
|
Us
|
Green
Red
|
Voltage 18 V<= US<=30 V
Voltage US<18 V or US>30 V
|
UL
|
Green
Red
|
Voltage 18 V<= US<=30 V
Voltage US<18 V or US>30 V
|
Ethernet Active M12 Distribution Block
|
|
|
|
|
|
|