Home > Relays > Phase Monitor Relays >

Macromatic PC1MDUL DIN-Rail Mount 190-600V Phase Monitor Relay

Macromatic PC1MDUL Phase Monitor Relay
Macromatic PC1MDUL DIN-Rail Mount 190-600V Phase Monitor Relay


 
Alternative Views:


Price: $444.42
Note: Ships in 5-10 Business Days
MFG P/N: PC1MDUL
MFG: Macromatic
Weight (lbs): 0.35



Availability:
In Stock
Product Code: PC1MDUL
Qty:

Description
 

The Macromatic PC1MDUL is a multi-detection phase monitor relay with communication capability. This DIN-Rail mount relay has a monitored voltage range of 190-600V. It monitors against 5 different types of phase errors and has an output of 5A SPDT. The LED shows the current status or specifies a particular phase error. Undervoltage trip point, trip delay, restart delay, unbalance trip point, and line-to-line voltage are all adjustable via turn knobs. The PC1MDUL features a 60 mm wide housing which is mountable on a 35mm DIN-Rail. It communicates through Modbus TCP for status and measurement updates in real time. Note: Image is an approximation. Actual part may differ.

Monitors For:

  • Phase Loss
  • Phase Reversal
  • Phase Unbalance
  • Undervoltage
  • Overvoltage

Specifications

  • Relay Function- Multi-Detection
  • Monitored Voltage- 190-600V AC
  • Output- 5A SPDT
  • Min. Voltage- 30V AC
  • Max. Voltage- 660V AC
  • Power Consumption- 3VA
  • Phase Loss- Trips on Phase L1, L2, or L3 loss
  • Phase Reversal- Trips if rotation is something other than L1-L2-L3
  • Phase Unbalance- Adjustable from 2-10% unbalance
    Trips when one of the 3 lines diverges from the average of all 3 by more than the adjusted set point for longer than the adjusted delay. Resets at 80% of the unbalance trip setting.
  • Undervoltage- Adjustable from 80-95% of line voltage
    Trips when the average of all 3 lines is less than the adjusted set point for longer than the adjusted delay
    Resets at +2% of the undervoltage trip setting
  • Overvoltage- Adjustable from 105-120% of line voltage
    Trips when the average of all 3 lines is greater than the adjusted set point for longer than the adjusted delay
    Resets at -2% of the overvoltage trip setting
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- SPDT 5 A @ 250V AC, General Purpose;
    5 A @ 24V DC, Resistive;
    1/4HP @ 120V AC (N.O.)
    Minimum recommended: 12V DC @ 100 mA
  • Life- Mechanical: 30 million closures at no load, 72,000 operations per hour max.
    Electrical: 100,000 closures at full load, 360 operations per hour max.
  • Response Time- Restart: 1 - 300 sec adjustable
    Phase Loss & Reversal: 100ms fixed
    Phase Unbalance Normal: 0.3 - 30 sec adjustable
    Phase Unbalance Severe: 0.3 - 2 sec
    Undervoltage & Overvoltage: 0.3 - 30 sec adjustable
  • Modbus TCP- RJ45 socket, Connection Speed: 10/100 Mb full & half duplex, IP addressing, static (default), dynamic (DHCP)
  • Dimensions- 4.36" Height x 2.36" Width x 2.6" Depth
  • Approvals- UL & CUL Listed

The PC1MDUL energizes when the line voltage is applied and the phase rotation is correct. It de-energizes (after a trip delay) if a fault is detected. The relay will energize again automatically once the fault is corrected. It can be re-energized manually if a momentary normally closed switch is attached to terminals 5 & 6.

This relay is ideal for automation applications that use a connected control system to monitor three-phase equipment. The PC1MDUL uses "True RMS voltage measurement" which gives more precise monitoring of phases and voltages. Besides mounting on a DIN-Rail, this relay can also be panel mounted using two #8 screws inserted through extended clips on the back of the housing. It can be replaced without removing wires due to the pluggable terminal blocks on the input and output sides.

Macromatic PC1MDUL Relay Installation Manual

Macromatic Three Phase Monitor Relay Comparison Chart

Three Phase Monitor Relay with Communication PC1MDUL

Additional Product Information