Macromatic Three Phase Monitor Relay Comparison Chart

Macromatic · Products for Automation

Three Phase Monitor Relay Comparison

Macromatic three-phase monitor relays detect phase and voltage faults that can affect motors and equipment. Also called phase protection or phase control relays, they are used in car wash facilities, elevators, packaging equipment, HVAC systems, irrigation and pump controls. Compare plug-in and DIN-rail models below to match the protection functions, settings and output contacts to your application.

Compare protection, mounting and output contacts

Click or tap on a series name to view products.

Series Housing Type Phase Reversal Phase Loss Phase Unbalance Undervoltage Overvoltage Output Approvals
PCP Plug-in Yes No No No No SPDT 10 A cURus, cULus (with socket), CE
PLP Plug-in Yes Yes No No No SPDT 10 A cURus, cULus (with socket), CE
PAP Plug-in Yes Yes No Adjustable 75–95% No SPDT 10 A cURus, cULus (with socket), CE
PJPU-FA8X Plug-in Yes Yes Indication only at 6% Fixed at 90% No SPDT + SPNO 5 A cURus, cULus (with socket), CE
PMP Plug-in Yes Yes Adjustable 2–10% Adjustable 80–95% Fixed at 110% SPDT 10 A cURus, cULus (with socket), CE
PMPU-FA8 Plug-in Yes Yes Fixed at 6% Fixed at 90% Fixed at 110% SPDT 10 A cURus, cULus (with socket), CE
PMPU-FA8X Plug-in Yes Yes Fixed at 6% Fixed at 90% Fixed at 110% SPDT + SPNO 5 A cURus, cULus (with socket), CE
PMPU-FA12X Plug-in Yes Yes Fixed at 6% Fixed at 90% Fixed at 110% DPDT 5 A cURus, cULus (with socket), CE
PMD DIN-rail Yes Yes Adjustable 2–10% Adjustable 80–95% Fixed at 110% DPDT 10 A cULus, CE
PBDU DIN-rail Yes Yes Adjustable 5–25% No No SPDT 5 A cULus, CE
PC DIN-rail / Modbus TCP Yes Yes Adjustable 2–10% Adjustable 80–95% Adjustable 105–120% SPDT 5 A cULus

Understand the settings: Undervoltage and overvoltage percentages refer to the nominal or selected line-to-line voltage. Phase unbalance percentages describe the difference between phase voltages, not an undervoltage setting. PJPU-FA8X has phase unbalance indication only at 6%, it does not trip the relay.

Narrow your relay selection

Start with the faults you need to detect

PCP covers phase reversal, while PLP adds phase loss protection. PAP adds adjustable undervoltage detection. For phase reversal, phase loss, phase unbalance, undervoltage and overvoltage protection together, compare PMP, PMPU-FA8, PMPU-FA8X, PMPU-FA12X, PMD and PC.

Choose fixed or adjustable settings

The PMPU-FA8, PMPU-FA8X and PMPU-FA12X use fixed thresholds of 6% phase unbalance, 90% undervoltage and 110% overvoltage. PMP and PMD offer adjustable unbalance and undervoltage settings. PC also provides adjustable overvoltage protection from 105–120%.

Match the panel and control circuit

Choose a plug-in relay for socket mounting or a DIN-rail model for direct panel installation. Compare SPDT, SPDT + SPNO and DPDT contacts against your circuit requirements. The PC model linked above, PC1MDUL, combines DIN-rail mounting with Modbus TCP communication and a 5 A SPDT output.

Before ordering a phase monitor relay

  • Confirm the exact model supports your system voltage and required fault protection.
  • Match the output contact arrangement and rating to the control circuit.
  • Check trip delay, restart delay and reset behavior in the model documentation.
  • For plug-in models, select the compatible socket and verify any socket-dependent approvals.