Home > Relays > Phase Monitor Relays >

Macromatic PAP208 208V Plug-in Phase Monitor Relay

Macromatic PAP208
Macromatic PAP208 208V Plug-in Phase Monitor Relay


 
Alternative Views:


Price: $84.21
MFG P/N: PAP208
MFG: Macromatic
Weight (lbs): 0.3

Quantity in Stock :2


Availability:
In Stock
Product Code: PAP208
Qty:

Description
 

The Macromatic PAP208 is a three phase monitor relay. This 8 pin plug in relay has a nominal voltage of 208V. It monitors against phase reversal, phase loss and undervoltage with an output of 10A SPDT. It features an LED that glows green when everything is functioning correctly and glows or blinks red when an error is detected. The diagram on top of the relay depicts how the LED will indicate the current status. The PAP208 uses an 8 pin 70169-D octal socket. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Three Phase
  • Nominal Voltage- 208V AC
  • Minimum Voltage- 156 V
  • Maximum Voltage- 550 V
  • Power Consumption- < 40VA
  • Output- 10A SPDT
  • Phase Reversal- Trips if rotation is something other than A-B-C
  • Phase Loss- Trips if Phase A, B or C is lost
  • Undervoltage- Adjustable from 156-198V, Trips when the average of all 3 lines is less than the set point for longer than the trip delay
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10A @ 277V AC / 7A @ 30V DC, 1 HP @ 250V AC, 1/2HP @ 125V AC, C300 Pilot Duty
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Response Time- Restart: 1 sec, Phase Loss/Reversal: 100ms, Undervoltage: 4 sec
  • Dimensions- 2.4" Height x 1.7" Width x 3.5" Depth
  • Approvals- UL and CUL Recognized, CE, C-UL-US Listed (with Socket)

As part of the PAP series, the PAP208 utilizes "True RMS voltage measurement". True RMS voltage measurement uses analog to digital sensing circuitry to provide more precise monitoring of phases and voltages. A unique feature in the PAP208 is that even if a phase is lost, it can still monitor all the voltages while indicating the fault. When the phases are detected in the right order without going below the undervoltage, the unit is energized. Undervoltage is adjustable from 75-95% of the nominal voltage. The unit is de-energized after a short time delay when any one of these phase errors is detected, and will stay in that mode until the error is fixed.

Macromatic PAP Series Relay Installation Manual

Macromatic Three Phase Monitor Relay Comparison Chart

Phase Monitor Relay

Additional Product Information

Related Products
Macromatic 70166 Hold Down Spring Macromatic 70169-D 8 Pin Octal Socket
Price: $5.09

Add
Price: $5.69

Add
Macromatic Hold Down Spring Macromatic 70169-D 8 Pin Octal Socket