General Data
|
|
Operating Voltage
|
9.6V - 32V DC
|
|
Buffer Time
|
Min. 10 milliseconds at 24V DC
|
|
Current Consumption
|
Typically 210 mA at 24V DC (without data), max 270 mA at 24V DC (with
data)
|
|
Overload Current Protection at Input
|
Non-changeable fuse
|
|
Dimensions
|
1.85" Width x 5.31" Height x 4.37" Depth
|
|
Weight
|
0.529 pounds
|
|
Ambient Temperature
|
32 F to 140 F
|
|
Storage Temperature
|
-40 F to 176 F
|
|
Humidity
|
10 - 95% (non-condensing)
|
|
Atmospheric Pressure
|
Min. 79 kPa
|
|
IP Protection
|
IP 20
|
|
Radio Disturbance Characteristics
|
EN 55022 Class A, CFR-47 Part 15 Class A
|
|
Immunity
|
Electrostatic discharge - EN 61000-4-2 Level 3
Electromagnetic
fields - EN 61000-4-3 Level 3
Bursts - EN 61000-4-4 Level 3 Surge
- EN 61000-4-5
Conducted Disturbance EN 61000-4-6 Level 3
|
|
Mechanical Service Conditions
|
Vibrations - IEC 60068-2-6 Test Fc
Shocks - IEC 60068-2-27 Test
Ea
|
|
Interfaces
|
4 x 100BaseTX shielded RJ45 ports
1 x 5 pole mountable terminal
block
|
|
Displays
|
P1, P2: Power
DA:Data FAULT STAT 1 to STAT 4: link status
per port
|
|
Network size -
Class II Repeater
|
|
SOP
|
46 BT (1 BT = 10 ns)
|
|
SOJ
|
46 BT
|
|
PDV
|
92 BT
|
|
Network size - TP Line Length
|
|
Length of Twisted Pair
|
Max. 328 Feet
|
|
Scope of delivery
|
|
Scope of delivery
|
device, terminal block, operating manual
|