Home > Relays > Voltage Monitor Relays >

Macromatic VAKP110D 110V DC Over/Undervoltage Monitor Relay


Macromatic VAKP110D Over/Undervoltage Monitor Relay
Macromatic VAKP110D 110V DC Over/Undervoltage Monitor Relay
 
Alternative Views:


Price: $85.08
Note: Delivery: 2-5 Business Days
MFG P/N: VAKP110D
MFG: Macromatic
Weight (lbs): 0.3

Quantity in Stock :2


Availability:
In Stock
Product Code: VAKP110D
Qty:

Description
 

The Macromatic VAKP110D is a voltage monitor relay. This 8 Pin plug-in relay has a nominal voltage of 110V DC. It checks for over or under voltage errors, with an output of 10A DPDT. The VAKP110D has an adjustable pick-up voltage & drop-out voltage, with an adjustable drop-out time delay ranging from 0.1-10 sec. It has an LED indicator that is red when the unit is energized or green when it is not. It uses an 8 Pin 70169-D octal socket. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Over/Undervoltage
  • Nominal Voltage- 110V DC
  • Output- 10A DPDT
  • Drop-out Time Delay- 0.1-10 sec
  • Pick-up Voltage Range- 83-138V DC
  • Drop-out Voltage Range- 62-130V DC (75-95% of Pick-Up)
  • Load- <2VA
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Voltage Tolerance- +/-50% of Nominal Voltage
  • Output Contacts- 10A @ 240V AC, 7A @ 30V DC, 1/4HP @ 120/240V AC, C300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Response Time- Pick-up: 0.5 sec, Drop-out: 0.1-10 sec
  • Reset- Automatic
  • Transient Protection- 2000V for IEC 61000-4-5 Level 3 (+/-2kV)
  • Dimensions- 2.4" Height x 1.7" Width x 3.5" Depth
  • Approvals- UL and CUL recognized, CE, UL & CUL listed (with Socket)

When the voltage goes above the preset pick-up voltage (83-138V DC), then the unit is energized. If the voltage drops below the preset drop-out for a longer duration than the drop-out time delay, then it de-energizes. Whether the VAKP110D operates for undervoltage or overvoltage protection is based on the kind of output contacts being used.

Overvoltage
Overvoltage protection makes use of a normally closed contact. The voltage needs to stay below the preset pick-up voltage for the load to be energized while the relay itself remains de-energized. If the voltage goes above the pick-up, the reverse happens, until voltage goes below the preset drop-out.

Undervoltage
Undervoltage monitoring requires a normally open contact. The load stays on and the relay is energized if the voltage stays above the preset pick-up. Voltage going below the preset drop-out de-energizes both the load and the relay.

Macromatic VAKP Series Relay Installation Instructions

110VDC Voltage Monitor Relay Macromatic VAKP110D

Additional Product Information

Related Products
Macromatic 70166 Hold Down Spring Macromatic 70169-D 8 Pin Octal Socket
Price: $1.59