Timer / Real-Time Clock
Red Lion PAXCK000 PAX Series Panel Meter - Timer & Real-Time Clock
6 digit red LED 1/8 DIN panel meter for elapsed timing, preset timing, real-time clock/date display, and cycle counting.
✓ Timer, Clock, Date & Counter Display in One 1/8 DIN Meter
Functions: elapsed timer, preset timer, real-time clock, date display, and cycle counter
Overview
The
Red Lion PAXCK000 PAX series panel meter combines timer, clock, date, and counter functions in a compact 1/8 DIN housing. It features a 6 digit red sunlight readable LED display, AC power input, and inputs from sources such as switch contacts or CMOS and TTL circuit outputs.6 Digit DisplayReal-Time ClockIP65 Front
Five front function keys, including three programmable keys, allow the meter to be configured for the application. Optional digital output and communication cards expand the unit with up to four setpoint outputs plus RS232, RS485, Modbus, DeviceNet, and Profibus-DP capability.
⏱ Multi-Function Timing Control
Timing Range: 23 selectable ranges with ±0.01% timing accuracy and 0.001 second minimum digit resolution.
Display Modes: Shows timer, cycle counter, date, and real-time clock information from one front-panel display.
Clock Capability: Supports 12 or 24 hour formats, multiple date formats, automatic Daylight Savings Time adjustment, and synchronization between multiple PAXCK units.
Key Features
- 1/8 DIN housing: compact panel-mount format
- 6 digit red LED display: sunlight readable 0.56" digits
- Elapsed timer with preset capability: flexible timing control
- Real-time clock: clock and date display functions
- 4 display modes: timer, clock, date, and counter
- Cycle counting capability: tracks process cycles
- Programmable function keys/user inputs: front-panel customization
- 4 setpoint alarm outputs: available with optional output card
- Communication and bus capability: available with option cards
- Crimson programming software: supports setup and configuration
- NEMA 4X/IP65 front panel: protected face rating
- Parameter lockout: setup values can be partially or completely locked
✅ Why Choose This Panel Meter?
The PAXCK000 is useful when a panel needs more than a basic timer. It can serve as an elapsed timer, preset timer, cycle counter, date display, and real-time clock while still allowing output and communication expansion through field-installable option cards.
Applications
Use the PAXCK000 where one panel display needs timer, clock, date, and count functions:
- Machine cycle timing
- Preset process timing
- Plant floor clock and date display
- Cycle counting and production tracking
- Synchronized time displays across multiple PAXCK units
⚠️ Important Application Info
Ballast/bypass notes do not apply to this product.
Use the user manual for wiring and setup. Maintain the required power, input, isolation, and enclosure ratings for the installation.
Parameter lockout can help prevent unauthorized setup changes after commissioning.
Performance Benefits
- Combines multiple timing and clock functions in one panel meter
- Reduces panel components by adding optional outputs and communication cards
- Sunlight readable red LED display improves visibility
- Front-panel NEMA 4X/IP65 rating supports industrial enclosure use
🔧 Field Upgradeable Design
Optional cards can add setpoint outputs and communication/bus capability, allowing the same base meter to support more advanced control and monitoring applications.
Specifications
|
Brand
|
Red Lion
|
|
Model
|
PAXCK000
|
|
Series
|
PAX
|
|
Type
|
Timer / Real-Time Clock Panel Meter
|
|
Housing
|
1/8 DIN
|
|
Display Color
|
Red LED
|
Inputs & Display
|
Display
|
6 digit, 0.56" (14.2 mm) red sunlight readable LED
|
|
Display Functions
|
Timer, cycle counter, date, and real-time clock
|
|
Timer Range
|
23 selectable ranges
|
|
Timing Accuracy
|
±0.01%
|
|
Minimum Resolution
|
0.001 sec.
|
|
User Inputs
|
Three programmable user inputs
|
|
Input Sources
|
Switch contacts, CMOS, and TTL circuit outputs
|
Power & Outputs
|
Power Input
|
85 to 250 VAC, 50/60 Hz, 18 VA
|
|
Isolation
|
2300 Vrms for 1 min. to all inputs and outputs
|
|
Sensor Power
|
12 VDC, ±10%, 100 mA max., short circuit protected
|
|
Output Options
|
Up to 4 setpoint outputs with optional digital output card
|
|
Communication Options
|
RS232, RS485, Modbus, DeviceNet, and Profibus-DP with option cards
|
Environment
|
Front Rating
|
NEMA 4X / IP65
|
|
Rear Rating
|
IP20
|
|
Operating Temp
|
0°C to 50°C (32°F to 122°F)
|
|
Storage Temp
|
-40°C to 60°C (-40°F to 140°F)
|
|
Humidity
|
85% max. relative humidity, non-condensing
|
Physical
|
Dimensions
|
1.95" x 3.8" x 4.2"
|
|
Connection
|
High Compression Cage-Clamp Terminal Block
|
|
Wire Strip Length
|
0.3" (7.5 mm)
|
|
Wire Gauge
|
30–14 AWG copper wire
|
|
Torque
|
4.5 inch-lbs (0.51 N-m) max.
|
Certifications
|
Compliance
|
CE Approved, RoHS Compliant
|
|
Safety
|
UL Recognized Component File #E179259; UL Listed File #E137808
|
|
Standards
|
EN 61326-1, CISPR 11 Class A, EN 61010-1, EN 61010-2-030
|
|
|
 |
 |
 |
 |

|