Red Lion PAXR0020 PAX Rate Panel Meter, 5 Digit Sunlight Readable LED, 1/8 DIN, 85-250 VAC
PAX series rate panel meter with 5-digit sunlight readable red LED display, 1/8 DIN housing, programmable user inputs, min/max rate memory, optional setpoint alarm outputs, and 85-250 VAC input power.
Why Choose the Red Lion PAXR0020 Rate Panel Meter?
The Red Lion PAXR0020 PAX series rate panel meter is made for industrial rate indication where a bright, sunlight readable 5-digit display is needed at the machine or control panel. The 0.56" red LED readout supports rate values up to 99999 and includes annunciators for rate, high rate, low rate, and optional setpoint output states.
This meter accepts switch contact, CMOS, TTL, magnetic pickup, and RLC sensor inputs, and it supports directional, uni-directional, and quadrature signals. Three programmable user inputs, adjustable brightness, min/max rate memory, and parameter lockout give operators flexible monitoring without leaving setup settings exposed after commissioning.
☀️ Sunlight Readable LED
5-digit 0.56" red display with adjustable brightness for industrial panels
⚡ 34 kHz Max Frequency
Rate display supports 0.01 Hz minimum frequency up to 34 kHz maximum
🔁 Flexible Signal Inputs
Works with switch contacts, CMOS/TTL outputs, magnetic pickups, and RLC sensors
🚨 Optional Setpoints
Four setpoint alarm outputs can be added with an optional digital output plug-in card
⚠️ Use Safeguards for Control Applications
This panel meter is not made to directly command motors, valves, or actuators without safeguards. Use the proper output card, interlocks, protective circuits, and machine-control design practices when setpoints are used in an industrial control system.
📋 Rate Monitoring Uses
The PAXR0020 is suited for industrial rate indication and machine monitoring.
Use it for speed display, production rate monitoring, high/low rate indication, min/max rate capture, equipment status display, and applications where directional, uni-directional, or quadrature signals need to be converted into an operator-readable rate value.
Key Features & Benefits
- 1/8 DIN housing
- 5-digit red LED display
- Rate indication
- Programmable function keys and user inputs
- Four setpoint alarm outputs available with optional card
- Min/max rate displays
- 85 to 250 VAC input power
- NEMA 4X/IP65 rated front panel
- Red LEDs readable in bright sunlight
- Adjustable display brightness
- MAX and MIN reading memory with programmable capture time
- Parameters can be completely or partially locked after setup
- Not made to directly command motors, valves, or actuators without safeguards
Technical Specifications
|
Brand
|
Red Lion
|
|
Series
|
PAX
|
|
Product Type
|
Rate Panel Meter
|
|
Display
|
5 digit, 0.56" (14.2 mm) red sunlight readable LED
|
|
Display Annunciators
|
r = rate; H = high rate; L = low rate; SP1-SP4 = setpoint output state
|
|
Housing / Panel Size
|
1/8 DIN
|
|
Input Power
|
85 to 250 VAC, 50/60 Hz, 18 VA
|
|
Isolation
|
2300 Vrms for 1 minute to all inputs and outputs; 300 V working
|
|
Sensor Power
|
12 VDC, ±10%, 100 mA max.; short circuit protected
|
|
Memory
|
Nonvolatile memory retains programmable parameters and display values
|
|
User Inputs
|
Three programmable user inputs; 30 VDC max. continuous input; jumper-selectable sink/source logic; 6 msec typical response time, function dependent
|
|
Rate Display Accuracy
|
±0.01%
|
|
Rate Frequency Range
|
0.01 Hz min. to 34 kHz max.
|
|
Maximum Display
|
5 digits: 99999
|
|
Adjustable Display Update
|
0.1 to 99.9 seconds, low update
|
|
Input A - Logic
|
VIL = 1.5 V max.; VIH = 3.75 V min.
|
|
Input A - Current Sinking
|
Internal 7.8 KOhm pull-up to +12 VDC; IMAX = 1.9 mA
|
|
Input A - Current Sourcing
|
Internal 3.9 KOhm pull-down; 7.3 mA max. at 28 VDC; VMAX = 30 VDC
|
|
Magnetic Pickup Input
|
200 mV peak sensitivity; 100 mV hysteresis; 3.9 KOhm input impedance at 60 Hz; ±40 V peak / 30 Vrms max. input voltage
|
|
Output Response Time
|
25 microsec.; add 6 msec typical if a relay card is installed
|
|
Timed Output Accuracy
|
Rate = ±0.01% + 20 msec.
|
|
Front Panel Rating
|
NEMA 4X/IP65, face only
|
|
Rear Rating
|
IP20, rear of unit
|
|
Operating Temperature
|
0°C to 50°C (32°F to 122°F)
|
|
Storage Temperature
|
-40°C to 60°C (-40°F to 140°F)
|
|
Humidity
|
85% max. relative humidity, non-condensing
|
|
Vibration
|
IEC 68-2-6; operational 5 to 150 Hz at 2 g
|
|
Shock
|
IEC 68-2-27; operational 25 g, 10 g relay
|
|
Altitude
|
Up to 2000 meters
|
|
Construction
|
One-piece bezel/case, flame resistant construction, synthetic rubber keypad, panel gasket, and mounting clip
|
|
Connection
|
High compression cage-clamp terminal block
|
|
Wire Strip Length
|
0.3" (7.5 mm)
|
|
Wire Gauge
|
30-14 AWG copper wire
|
|
Torque
|
4.5 inch-lbs (0.51 N-m) max.
|
|
Dimensions
|
1.95" x 3.8" x 4.2"
|
|
Standards / Compliance
|
CE Approved; EN 61326-1 immunity to industrial locations; CISPR 11 Class A emissions; EN 61010-1; EN 61010-2-030; RoHS Compliant; UL Recognized Component File #E179259; UL Listed File #E137808; Type 4X face rating; IP65 face rating; IP20 rear rating
|