Home > Relays > Percentage Timers >

Macromatic PTA2001HB Percentage Timer, 1 Hr, 120V AC, No Memory


Macromatic Percentage Timer, 1 Hour, 120V AC, No Memory
Macromatic PTA2001HB Percentage Timer, 1 Hr, 120V AC, No Memory
 
Alternative Views:


Price: $164.20
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: PTA2001HB
MFG: Macromatic
Weight (lbs): 0.14



Availability:
In Stock
Product Code: PTA2001HB
Qty:

Description
 

The Macromatic PTA2001HB is a percentage timer. This panel mount timer relay has an input voltage of 120V AC with an output of 10A SPNO and a timer range of 1 hour. It is used for instances when the ON time when used a percentage of a total cycle time has to be adjustable. This timer is useful for applications such as irrigation, heating & cooling, motors, and chemical feeding. It has an integrated potentiometer for time delay adjustment. An LED indicator on top shows the relay status. Termination is possible with bare wire or crimp terminals. Mounting hardware included. Note: Image is for reference. Actual part may differ.

Specifications

  • Relay Function- Percentage Timer w/o Memory
  • Relay Timer Range- 1 Hour
  • Input Voltage- 120V AC
  • Output- 10A SPNO
  • Voltage Tolerance- +10/-15% of nominal at 50/60 Hz
  • Load- Max of 3 VA
  • Setting Accuracy- +/- 2%
  • Setting Precision- +/- 1% of total cycle time
  • Dial Resolution- Dial settings marked in 1% increments
  • Repeat Accuracy- +/- 0.1% or +/- 0.04 seconds, whichever is greater
  • Reset Time- 300ms
  • Start Up Time- 0.05 seconds
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10A @ 240VAC / 7A @ 28VDC SPNO, 1/4 HP @ 120VAC
  • Lifespan- Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Termination- Pressure Clamp Screw Terminals, #12-22 AWG wire, solid, stranded wire; Recommended tightening torque 7 in-lbs. (12 in-lbs max)
  • Dimensions- 3.5" Height x 3.5" Width x 4.1" Length
  • Approvals- UL & CUL Listed, CE

When the input voltage is introduced, the percentage timer relay energizes and the ON time delay (t1) starts. T1 is adjustable as a percentage of the total ON/OFF cycle time (t2), which is one hour. When t1 ends, the relay de-energizes for the rest of the timing cycle. The ON/OFF sequence will then repeat. This continues until the input voltage is removed. The sequence resets itself if the input voltage is taken out. 100% will keep the output constantly energized and 0% will keep it constantly de-energized. The LED on top is steady during the OFF sequence and blinks during the ON sequence.

Macromatic Percentage Timer Installation Manual

PTA2001HB 1 Hour 120V Percentage Timer without Memory


Related Products
Macromatic 70600 Terminal Cover for Percentage Timers
Price: $0.92

Add
Macromatic Terminal Cover



Sealcon M16 Connector, Elongated, Female Straight, 18 Pin $61.50
Seifert 4732902003 Filter Assembly 325mm x 325mm Black $52.45
Sealcon M16 Connector, Female Straight, 10 Pin, 5-9 mm $34.49
Sealcon CD36AA-FE PG 36 Dome .94" - 1.26" (24 - 32 mm) EMI/RFI Proof Cord Grip $88.71
Macromatic LCP1B100F4 240V Single Probe Liquid Level Relay, Pump Down, 4.7K to 100K, 4 Sec Delay $93.62
Sealcon CD32MA-BK Black M32 Dome .71" - .98" (18 - 25 mm) O.D. Cord Grip $4.42
DuraChoice T3D60250 Bi-Metal Thermometer, 3" Dial, 6" Stem, 0-250 F $22.48
Jorc 5523 115V AC COMBO-D-LUX Timer Controlled Drain, Dual Inlet, 0-230 PSI $235.20
ILME CAP-16L C-Type Surface Mount Housing, Size 77.27, Single Lever, PG 21 $45.61