Home > Relays > Current Sensing Relays >

Macromatic CUH05A1AG Under Current Sensing Relay, 0.5-5A, 0.15-7 Sec, 240V, 4 Sec Delay


Macromatic CUH05A1AG Under Current Sensing Relay
Macromatic CUH05A1AG Under Current Sensing Relay, 0.5-5A, 0.15-7 Sec, 240V, 4 Sec Delay
 
Alternative Views:


Price: $89.05
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: CUH05A1AG
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: CUH05A1AG
Qty:

Description
 

The Macromatic CUH05A1AG is a current sensing relay. This encapsulated relay has an input voltage of 240V AC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 0.5-5A and a trip time delay of 0.15-7 seconds. There is a 4 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 0.5-5 Amps
  • Time Trip Delay- 0.15-7 seconds
  • Sensing Time Delay on Startup- 4 Seconds
  • Input Voltage- 240V AC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-25A Turns; 150A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 4 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH05A1AG has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

Encapsulated Under Current Sensing Relay CUH05A1AG




Jorc 3622 U1 115V AC SMART-GUARD-MINI-AL Level Sensing Drain w/ Alarm, 1/2" NPT, 0-230 PSI, NO $313.56
Meltric 63-38163 DSN30 30A, 208V, 3P+G Male Inlet $131.27
AerosUSA 1732052442 DES-PM 24/42G Cable Entry Plate, 42 Entries $16.38
Boxco BC-ATP-405020 Enclosure, 400x500x200, Clear Hinged Lid, ABS Plastic $103.09
Sealcon ED25MR-GY Gray M25 Elbow Dome .35" - .63" (9 - 16 mm) O.D. Cord Grip $22.64
Sealcon CD21NS-02 Gray 3/4" NPT Dome .24" x .55" (6 x 14 mm) Romex Cord Grip $4.22
Coxreels 15360-11.5 Top Rewind 3 Way Roller Bracket, 11.5", 1175 & 1185 Series $345.87
Mencom MIN-6MPM-FW MIN Size I Plug, 6 Pole, Male Straight, 5-13 mm, Male Thread $35.71