The Macromatic VAKP120A is a voltage monitor relay. This 8 Pin plug-in relay has a nominal voltage of 120V. It monitors against over or under voltage errors and has an output of 10A DPDT. The VAKP120A features an adjustable pick-up voltage, drop-out voltage and an adjustable time delay ranging from 0.1-10 sec. It features an LED that is red when the unit is energized or green when it is not. It uses an 8 Pin 70169-D octal socket. Whether the relay operates for undervoltage or overvoltage protection is subject to the kind of output contacts being used. Note: 24V version shown.

Specifications

  • Relay Function- Over/Undervoltage
  • Nominal Voltage- 120V AC
  • Output- 10A DPDT
  • Drop-out Time Delay- 0.1-10 sec
  • Pick-up Voltage Range- 90-150V AC
  • Drop-out Voltage Range- 68-142V AC (75-95% of Pick-Up)
  • Load- <2VA
  • Setting Accuracy- Max Setting (adjustable): +5%, -0%
    Min Setting (adjustable): +0%, -50%
    Fixed Voltage Setting: +/- 2%
  • Repeatability- <1%
  • Sensing Accuracy- Constant conditions within specs: +/- 2%
    Variable conditions within specs: +/- 5%
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Voltage Tolerance- +/-50% of Nominal Voltage
  • Output Contacts- 10A @ 240V AC, 7A @ 30V DC, 1/4HP @ 120/240V AC, C300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Response Time- Pick-up: 0.5 sec, Drop-out: 0.1-10 sec
  • Reset- Automatic
  • Transient Protection- 2000V for IEC 61000-4-5 Level 3 (+/-2kV)
  • Dimensions- 2.4" Height x 1.7" Width x 3.5" Depth
  • Approvals- UL and CUL recognized, CE, UL & CUL listed (with Socket)

When the voltage stays above the preset pick-up voltage (90-150V AC), then the unit is energized. If the voltage goes below the preset drop out for greater duration than the drop-out time delay, then it de-energizes.

Overvoltage
Overvoltage protection makes use of a normally closed contact. The voltage needs to stay below the preset pick-up voltage for the load to be energized while the relay itself remains de-energized. If the voltage goes above the pick-up, the reverse happens, until voltage goes below the preset drop-out.

Undervoltage
Undervoltage monitoring requires a normally open contact. The load stays on and the relay is energized if the voltage stays above the preset pick-up. Voltage going below the preset drop-out de-energizes both the load and the relay.

Macromatic VAKP Series Relay Installation Instructions

VAKP120A Over/Undervoltage Monitor Relay

Additional Product Information

Related Products
Macromatic 70169-D 8 Pin Octal Socket Macromatic 70166 Hold Down Spring
Price: $5.04

Add
Price: $1.59

Add
Macromatic 70169-D 8 Pin Octal Socket Macromatic Hold Down Spring



Meltric 555P0D35 DSN150 0.984 - 1.377" Santoprene Handle $288.31
Menics M16R-24G LED Indicator, 16 mm, Round Head, 24VDC, Green $7.63
Mencom MCVP-12MP-10M M23 Cordset, 12 Pole, Male, 6/2 Amp, 10 M $173.52
DuraChoice TW440 4" Thermowell, 1/2" NPT F x 1/2" NPT M, Stainless Steel 304 $17.25
Meltric 593P0N05 DSN60 1/2" NPT Aluminum Handle $106.81
Hirschmann Din 43650 Form A PG 9, 110-120V LED, MOV Suppression - EPDM Flat $8.39
Meltric 33-14042 DS20 20A, 480V, 2P+G Female Receptacle $282.11
Sealcon DM-12-BK M12 Black Nylon Dome Plug $0.31