Home > Relays > Time Delay Relays >

Macromatic THR-11666-04 Encapsulated Time Delay Relay, Off Delay, 12V, 0.05-5 Sec


Macromatic THR-11666-04 Time Delay Relay
Macromatic THR-11666-04 Encapsulated Time Delay Relay, Off Delay, 12V, 0.05-5 Sec
 
Alternative Views:


Price: $27.99
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: THR-11666-04
MFG: Macromatic
Weight (lbs): 0.5



Availability:
In Stock
Product Code: THR-11666-04
Qty:

Description
 

The Macromatic THR-11666-04 is an off delay Time Delay Relay. This encapsulated relay has an input voltage of 12V DC. It has an adjustable time range of 0.05 to 5 seconds. Time is adjusted by turning the blue dial at the top. The encasement of the unit is made for use under harsh conditions. The design is microprocessor-based to provide better functionality, and is perfect for high volume OEM applications. Note: Image is for reference, actual part may differ

Specifications

  • Relay Function- Off Delay
  • Mounting Style- Surface Mount with #8 or #10 Screw
  • Termination- 0.25" Male Quick Connect Terminals
  • Relay Timing Range- 0.05 - 5 seconds
  • Input Voltage- 12V DC
  • Output- 10 Amps SPDT
  • Voltage Tolerance- AC Operation: +10/-15% of nominal at 50/60 Hz. DC Operation: +10/-15% of nominal voltage
  • Load- Max. 2VA
  • Setting Accuracy- Maximum Setting (Adjustable): +5%, -0% Minimum Setting (Adjustable): +0%, -50% Fixed Time Delay: +/-2% or 50ms, whichever is greater
  • Repeat Accuracy- The greater amount of +/- 0.1% or +/- 0.04 Sec
  • Reset Time- 40ms
  • Startup Time- 0.05 seconds
  • Maintain Function Time- 0.01 seconds
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -45 C to 85 C (-49 F to 185 F);
  • Output Contacts- 10A @ 240VAC / 7A @ 28VDC SPDT, 1/4 hp @ 120VAC (N.O.)
  • Life- Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Overall Dimensions- 2" Height x 2" Width x 1.14" Depth
  • Approvals- C UR US, CE

With the Off Delay function, the relay energizes once the trigger is implemented. The time delay only starts once the trigger is taken out. After the time delay ends, the relay de-energizes. Re-introducing the trigger before the time delay finishes resets it, preventing the relay from de-energizing. The input voltage needs to be in place for the trigger to be successfully introduced

Macromatic THR Series Relay Installation Instructions

Explanation of Macromatic Time Delay Relay Timing Functions




Hirschmann 933366100 ELKA 3008 V M8 Cable Socket, 3 Pin, Female $19.07
HTP 12FC5000-ATEX M12 Connector, 5 Pin, Female Straight, PG 7, ATEX Approved $119.99
Sealcon VT22MR-BR M20 Dome .28" - .55" (7 - 14 mm) O.D. Extreme Temp Cord Grip $25.58
Kacon T16-170GD4 16 mm Green Pilot Lamp, 24V DC LED $17.32
Menics S10F-24B LED Indicator, 10mm, Flat Head, 24VDC, Blue, IP 67 $9.15