Home > Relays > Voltage Monitor Relays >

Macromatic VAKP024D 24V DC Over/Undervoltage Monitor Relay


Macromatic VAKP024D Over/Undervoltage Monitor Relay
Macromatic VAKP024D 24V DC Over/Undervoltage Monitor Relay
 
Alternative Views:


Price: $85.08
Note: Delivery: 2-5 Business Days
MFG P/N: VAKP024D
MFG: Macromatic
Weight (lbs): 0.3

Quantity in Stock :1


Availability:
In Stock
Product Code: VAKP024D
Qty:

Description
 

The Macromatic VAKP024D is a voltage monitor relay. This 8 Pin plug-in relay has a nominal voltage of 24V DC. It monitors against over or under voltage errors and has an output of 10A DPDT. The VAKP024D features an adjustable pick-up voltage, drop-out voltage and an adjustable time delay ranging from 0.1-10 sec. It features an LED that is red when the unit is energized or green when it is not. It uses an 8 Pin 70169-D octal socket. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Over/Undervoltage
  • Nominal Voltage- 24V DC
  • Output- 10A DPDT
  • Drop-out Time Delay- 0.1-10 sec
  • Pick-up Voltage Range- 18-30V DC
  • Drop-out Voltage Range- 14-28V DC (75-95% of Pick-Up)
  • Load- <2VA
  • Setting Accuracy- Max Setting (adjustable): +5%, -0%
    Min Setting (adjustable): +0%, -50%
    Fixed Voltage Setting: +/- 2%
  • Repeatability- <1%
  • Sensing Accuracy- Constant conditions within specs: +/- 2%
    Variable conditions within specs: +/- 5%
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Voltage Tolerance- +/-50% of Nominal Voltage
  • Output Contacts- 10A @ 240V AC, 7A @ 30V DC, 1/4HP @ 120/240V AC, C300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Response Time- Pick-up: 0.5 sec, Drop-out: 0.1-10 sec
  • Reset- Automatic
  • Transient Protection- 2000V for IEC 61000-4-5 Level 3 (+/-2kV)
  • Dimensions- 2.4" Height x 1.7" Width x 3.5" Depth
  • Approvals- UL and CUL recognized, CE, UL & CUL listed (with Socket)

When the voltage stays above the preset pick-up voltage (18-30V DC), then the unit is energized. If the voltage goes below the preset drop out for greater duration than the drop-out time delay, then it de-energizes. Whether the VAKP024D operates for undervoltage or overvoltage protection is subject to the kind of output contacts being used.

Overvoltage
Overvoltage protection makes use of a normally closed contact. The voltage needs to stay below the preset pick-up voltage for the load to be energized while the relay itself remains de-energized. If the voltage goes above the pick-up, the reverse happens, until voltage goes below the preset drop-out.

Undervoltage
Undervoltage monitoring requires a normally open contact. The load stays on and the relay is energized if the voltage stays above the preset pick-up. Voltage going below the preset drop-out de-energizes both the load and the relay.

Macromatic VAKP Series Relay Installation Instructions

Macromatic VAKP024D 24V 8 Pin Voltage Monitor Relay

Additional Product Information

Related Products
Macromatic 70169-D 8 Pin Octal Socket Macromatic 70166 Hold Down Spring
Price: $5.04

Add
Price: $1.59

Add
Macromatic 70169-D 8 Pin Octal Socket Macromatic Hold Down Spring



Sealcon M16 Connector, Elongated, Female Straight, 18 Pin, 5-9 mm $61.50
Mencom CRC-M16 M16 to M20 Nickel Plated Brass Enlarger $3.26
DuraChoice PB254B-K02 Oil Filled Pressure Gauge, 2-1/2" Dial, 1/4" NPT, 0-2000 PSI, Back Mount $13.42
Sealcon M16 Rear Mount Panel Connector, Male, 3 Pin, 2 mm Contacts, w/ Flange $44.47
Sealcon M16 Connector, Female Straight, 3 Pin, 1 mm Contacts, 28-20 AWG $24.31
DuraChoice PB158B-V00 Oil Filled Vacuum Gauge, 1-1/2" Dial, 1/8" NPT, -30HG-0 PSI, Back Mount $11.99
GardTec SC162-W1 162mm Wire Form Fan Guard, Vertical Mounting Positions $1.68
Kacon T16-372WD4 16 mm White Maintained Push Button, DPDT, 24V DC LED $25.84
Boxco BC-CGP-192810 Enclosure, 190x280x100, Solid Gray Hinged Lid, Polycarbonate $42.78