Home > Panel Meters > C48 1/16 DIN Counters & Timers >

Red Lion C48TD105 Panel Meter, Dual Preset Timer, AC, Dual NPN OC Outputs, RS-485

Red Lion C48TD105 Panel Meter, Dual Preset Timer
Red Lion C48TD105 Panel Meter, Dual Preset Timer, AC, Dual NPN OC Outputs, RS-485


 
Alternative Views:


Price: $349.00
Note: Please call or email [email protected] for alternatives
MFG P/N: C48TD105
MFG: Red Lion
Weight (lbs): 0.38

Quantity in Stock :(Out of Stock)


Availability:
Out of Stock
Product Code: C48TD105
Qty:

Description
 

The Red Lion C48TD105 C48 series panel meter is a dual preset timer with dual NPN OC solid state outputs. It has a 2 line, 6 digit, transmissive backlit LCD display with 1/16 DIN housing. The backlit display shows a red readout on the main line and a green readout on the secondary line. The resistance to noise interference makes it perfect for industrial use. AC powered. Note: This timer is not intended to directly control motors, valves, or actuators that do not have safeguards.

Features

  • Two Presets
  • 12 Timing Range Modes
  • Dual Line, 6 Digit Transmissive LCD Display w/Backlighting
  • Red Top Line & Green Lower Line
  • Dual NPN OC Outputs
  • 85 to 250 VAC Input Power
  • NEMA 4X/IP65 - Front Panel
  • RS-485 Communications Capability
  • Status Indicators for Outputs
  • Programmable User Inputs
  • Function Keys on Front Panel
  • Lightweight Black Plastic Housing Withstands Impact
  • Several Can be Stacked Horizontally or Vertically

Red Lion C48T Series User Manual

Specifications

Display
Main Display: 0.3" digits
Secondary Display: 0.2" digits
Annunciators: Value- PRS, 1, & 2; Output- 01 and 02
Power Requirements
AC Power: 85-250 VAC, 50/60 Hz, 9 VA max
DC Power: 11-14 VDC @ 150 mA max
Memory
Nonvolatile E2PROM retains all programmable parameters and timer values
Sensor Power
+12 VDC (+/- 15%) @100 mA max
Count Inputs A & B
Current Sourcing: 3.9KOhm pull-down, VIN max = 30 VDC
Current Sinking: 7.8KOhm pull-up to 12 VDC; ISNK = 1.8 mA max
Debounce: 50 Hz max
Lo Bias: VIL = 1.5 VDC max., VIH = 3.75 VDC min.
Hi Bias: VIL = 5.5 VDC max., VIH = 7.5 VDC min
User Inputs
Current Sinking: VIL = 1.5 VDC max, 22 KOhm pull-up to 5 VDC
Current Sourcing: VIH = 3.5 VDC min., VIN max = 30 VDC; 22 KOhm pulldown
Run/Stop Response Time: 250 usec max.
User Input Response Time: 5 msec max.
Time Accuracy: +/- 0.01%
Outputs
Solid State: NPN Open Collector- ISNK = 100 mA max. @ VOL = 1.1 VDC max.; VOH = 30 VDC max.
Standards Compliance
UL & CUL Recognized
Electrostatic Discharge: EN 61000-4-2
Electromagnetic RF Fields: EN 61000-4-3
Fast Transients (burst): EN 61000-4-4
RF Conducted Interference: EN 61000-4-6
Simulation of Cordless Phone: ENV 50204
RF Interference: EN 55011
Physical
Operating Temperature: 0 C to 50 C (32 F to 122 F)
Storage Temperature: -40 C to 70 C (-40 F to 158 F)
Humidity: 85% max. relative humidity (non-condensing) from 0 C to 50 C.
Altitude: Up to 2000 meters
Housing: Black Plastic
Electrical Connection: Wire clamping screw terminals
Dimensions: 1.95" x 1.95" x 4.54"
RS-485 Serial Communications
Baud Rate: Programmable from 1200 to 9600 baud
Address: Programmable from 0 to 99
Data Format: 10 Bit Frame, 1 start bit, 7 or 8 data bits, 1 or No Parity bit, & 1 stop bit
Parity: Programmable for Odd (7 data bits), Even (7 data bits), or None (8 data bits)

Dual Preset Timer Panel Meter C48TD105

Additional Product Information

This panel meter timer features 42 operating modes & 12 timing ranges, measuring from thousandths of a second up to minutes and hours. Timing can be set to constantly accumulate or reset for each power cycle. Decimal points keep the timing units (seconds, minutes, hours) separate on the display. It accommodates On Delay, Off Delay, Single Shot, & Repetitive Auto Cycling timing modes. Inputs include a Run/Stop Input, and three programmable User Inputs. The function keys on the front program operating modes & data values, change the display, and reset the timer. Data entry is done through digit entry or automatic scrolling. Run/Stop and User inputs can be sinking (active low) or sourcing (active high) through a single plug jumper. It is possible to achieve two way communication with a printer, computer, or other device through the RS-485 serial communication interface

Panel Meter Comparison Chart