Home > Relays > Time Delay Relays >

Macromatic THR-12266-04 Encapsulated Time Delay Relay, Single Shot Falling Edge, 12V, 0.05-5 Sec


Macromatic THR-12266-04 Time Delay Relay
Macromatic THR-12266-04 Encapsulated Time Delay Relay, Single Shot Falling Edge, 12V, 0.05-5 Sec
 
Alternative Views:


Price: $27.99
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: THR-12266-04
MFG: Macromatic
Weight (lbs): 0.5



Availability:
In Stock
Product Code: THR-12266-04
Qty:

Description
 

The Macromatic THR-12266-04 is a single shot falling edge Time Delay Relay. This encapsulated relay has an input voltage of 12V DC. It has an adjustable time range of 0.05 to 5 seconds. Time is adjusted by turning the blue dial at the top. The encasement of the unit is made for use under harsh conditions. The design is microprocessor-based to provide better functionality, and is perfect for high volume OEM applications. Note: Image is for reference, actual part may differ

Specifications

  • Relay Function- Single Shot Falling Edge
  • Mounting Style- Surface Mount with #8 or #10 Screw
  • Termination- 0.25" Male Quick Connect Terminals
  • Relay Timing Range- 0.05 - 5 seconds
  • Input Voltage- 12V DC
  • Output- 10 Amps SPDT
  • Voltage Tolerance- AC Operation: +10/-15% of nominal at 50/60 Hz. DC Operation: +10/-15% of nominal voltage
  • Load- Max. 2VA
  • Setting Accuracy- Maximum Setting (Adjustable): +5%, -0% Minimum Setting (Adjustable): +0%, -50% Fixed Time Delay: +/-2% or 50ms, whichever is greater
  • Repeat Accuracy- The greater amount of +/- 0.1% or +/- 0.04 Sec
  • Reset Time- 40ms
  • Startup Time- 0.05 seconds
  • Maintain Function Time- 0.01 seconds
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -45 C to 85 C (-49 F to 185 F);
  • Output Contacts- 10A @ 240VAC / 7A @ 28VDC SPDT, 1/4 hp @ 120VAC (N.O.)
  • Life- Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Overall Dimensions- 2" Height x 2" Width x 1.14" Depth
  • Approvals- C UR US, CE

With a Single Shot Falling Edge, the relay de-energizes when the trigger is implemented. Taking away the trigger energizes the relay and begins the time delay. After the time delay, it de-energizes again, and needs the trigger introduced and taken out to re-energize. Adding and taking away the trigger before the time delay ends will keep the relay energized.

Macromatic THR Series Relay Installation Instructions

Explanation of Macromatic Time Delay Relay Timing Functions




Z+F V30AE000030 Green Polypropylene Insulated End Sleeve, 6 AWG, 1.1" Length $0.06
Sealcon HP-48-BR-V PG 48 Nickel Plated Brass Hex Plug with Viton O-Ring $41.56
Mencom MDC-5FR-BM M12 Receptacle, 5 Pole, Female Straight, 4A, PG 9, Back Mount $18.53
Cable Tie Express 4-18-UV-1000 4" Nylon Miniature Cable Ties, Black, Bulk Pack 1000 Pcs $5.29
Sealcon HP-11-BR PG 11 Nickel Plated Brass Hex Plug $2.54
Deca A20F-3E02Q3G 22 mm Maintained Selector Switch, 3 Position, 2NC, 12V LED, Green $19.94
Macromatic THR-13162-35 Encapsulated Time Delay Relay, Repeat Cycle OFF, 120V, 1-100 Hr $32.02