IMO UB10D1030A 30A UL 489 Circuit Breaker, 1-pole, D Curve, 10kA
30A 1-pole D-curve miniature circuit breaker with thermo-magnetic protection, 10kA breaking capacity, DIN-rail mounting, and UL 489 approval.
Why Choose the IMO UB10D1030A Circuit Breaker?
The IMO Precision Controls UB10D1030A is a 30A 1-pole miniature circuit breaker for higher-current single-pole equipment branches requiring 30A protection and high-inrush tolerance. It is rated for 277V AC or 48V DC and provides UL 489 branch-circuit protection in industrial control panels, machinery, and distribution equipment when applied within its electrical ratings.
Thermo-magnetic operation combines a thermal response for sustained overloads with rapid magnetic response during severe faults. The D curve delays magnetic tripping until a higher multiple of rated current, helping prevent nuisance trips on loads with brief, high startup current. A contact-position indicator provides a clear visual reference during inspection and troubleshooting.
ā” 30A Rating
Protects a correctly sized 1-pole branch circuit rated for 30A
š D Trip Curve
10ā20 Ć In magnetic range supports loads with high startup current
š”ļø 10kA Capacity
Provides 10kA short-circuit breaking capacity for suitable electrical systems
ā
UL 489 Approved
Approved for branch-circuit protection when selected and installed correctly
ā ļø Coordinate the 30A 1-pole Breaker with the Load
Confirm the 30A rating, 1-pole configuration, conductor current, 277V AC or 48V DC rating, available fault current, D trip curve, ambient conditions, and equipment requirements before installation. A D-curve breaker does not replace separate motor-overload protection when the equipment or applicable code requires it.
š 30A D-Curve Magnetic Trip Range
The D-curve magnetic element operates at 10ā20 times rated current. For the UB10D1030A, this corresponds to an instantaneous magnetic range of approximately 300ā600A. The thermal element responds to sustained overloads. Confirm coordination with normal startup current and upstream or downstream protective devices.
Key Features & Benefits
- 1-pole DIN-rail mounting configuration
- Rated for 277V AC or 48V DC
- Approximate magnetic trip range of 300ā600A
- Thermo-magnetic overload and short-circuit protection
- Contact-position indicator for visual status checks
- 18ā3 AWG conductor range with 2.5 Nm fastening torque
- UL 489, IEC 60947-2, IEC 60898-1, and RoHS compliance
Technical Specifications
| Dimensions |
4.25" Length x 0.69" Width x 2.64" Depth (108mm x 17.5mm x 67mm) |
| Rated Current |
30 Amps |
| Voltage Rating |
277V AC / 48V DC |
| Number of Poles |
1 |
| Tripping Curve |
D (10-20 In) |
| Calibration Temperature |
104 F (40 C) |
| Operating Temperature |
-13 F to 131 F (-25 C to 55 C) |
| Rated Operational Frequency |
50/60 Hz |
| Short Circuit Breaking Capacity |
10kA |
| Lifespan |
20,000 Operations (Mechanical), 6000 Operations (Electrical) |
| Vibration Resistance |
+/- 1mm @ 5-25 Hz; 50 m/s² @ 25-150 Hz |
| Fastening Torque |
2.5 Nm (22.2 lb/in) |
| Wire Range |
18-3 AWG |
| NEMA Rating |
NEMA 1 (IP20 - Protection from objects 12.5 mm (0.5") in diameter or greater) |
| Approvals |
UL 489, IEC 60947-2 & IEC 60898-1, RoHS Compliant |
š 1-pole Breaker Selection and Installation Overview
1. Calculate the Load: Confirm that conductor current and connected equipment are compatible with a 30A protective device.
2. Verify Pole and Voltage Requirements: Confirm that the circuit requires 1 pole and operates within the 277V AC or 48V DC rating.
3. Check Fault and Inrush Current: Verify the available fault current, 10kA breaking capacity, and compatibility of the D curve with normal startup demand.
4. Mount and Terminate: Install on DIN rail using conductors within the specified 18ā3 AWG range and apply the listed 2.5 Nm terminal torque.
5. Inspect Before Energizing: Verify wiring, labeling, protective-device coordination, and code compliance before commissioning.
Circuit-breaker selection and installation must be completed by qualified personnel in accordance with the equipment documentation and applicable electrical codes.
š Typical Uses for the 30A 1-pole D-Curve Breaker
⢠Higher-current machinery auxiliaries ⢠Transformer and power-conversion equipment ⢠Industrial inductive-load branches ⢠AC or DC circuits requiring 30A D-curve protection
|
|
 |
 |
 |
 |

|