Home > Relays > Voltage Monitor Relays >

Macromatic VAKP120A 120V Over/Undervoltage Monitor Relay


Macromatic VAKP120A Over/Undervoltage Monitor Relay
Macromatic VAKP120A 120V Over/Undervoltage Monitor Relay
 
Alternative Views:


Price: $85.08
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: VAKP120A
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: VAKP120A
Qty:

Description
 

The Macromatic VAKP120A is a voltage monitor relay. This 8 Pin plug-in relay has a nominal voltage of 120V. It monitors against over or under voltage errors and has an output of 10A DPDT. The VAKP120A features an adjustable pick-up voltage, drop-out voltage and an adjustable time delay ranging from 0.1-10 sec. It features an LED that is red when the unit is energized or green when it is not. It uses an 8 Pin 70169-D octal socket. Whether the relay operates for undervoltage or overvoltage protection is subject to the kind of output contacts being used. Note: 24V version shown.

Specifications

  • Relay Function- Over/Undervoltage
  • Nominal Voltage- 120V AC
  • Output- 10A DPDT
  • Drop-out Time Delay- 0.1-10 sec
  • Pick-up Voltage Range- 90-150V AC
  • Drop-out Voltage Range- 68-142V AC (75-95% of Pick-Up)
  • Load- <2VA
  • Setting Accuracy- Max Setting (adjustable): +5%, -0%
    Min Setting (adjustable): +0%, -50%
    Fixed Voltage Setting: +/- 2%
  • Repeatability- <1%
  • Sensing Accuracy- Constant conditions within specs: +/- 2%
    Variable conditions within specs: +/- 5%
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Voltage Tolerance- +/-50% of Nominal Voltage
  • Output Contacts- 10A @ 240V AC, 7A @ 30V DC, 1/4HP @ 120/240V AC, C300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Response Time- Pick-up: 0.5 sec, Drop-out: 0.1-10 sec
  • Reset- Automatic
  • Transient Protection- 2000V for IEC 61000-4-5 Level 3 (+/-2kV)
  • Dimensions- 2.4" Height x 1.7" Width x 3.5" Depth
  • Approvals- UL and CUL recognized, CE, UL & CUL listed (with Socket)

When the voltage stays above the preset pick-up voltage (90-150V AC), then the unit is energized. If the voltage goes below the preset drop out for greater duration than the drop-out time delay, then it de-energizes.

Overvoltage
Overvoltage protection makes use of a normally closed contact. The voltage needs to stay below the preset pick-up voltage for the load to be energized while the relay itself remains de-energized. If the voltage goes above the pick-up, the reverse happens, until voltage goes below the preset drop-out.

Undervoltage
Undervoltage monitoring requires a normally open contact. The load stays on and the relay is energized if the voltage stays above the preset pick-up. Voltage going below the preset drop-out de-energizes both the load and the relay.

Macromatic VAKP Series Relay Installation Instructions

VAKP120A Over/Undervoltage Monitor Relay

Additional Product Information

Related Products
Macromatic 70166 Hold Down Spring Macromatic 70169-D 8 Pin Octal Socket
Price: $1.59

Add
Price: $5.04

Add
Macromatic Hold Down Spring Macromatic 70169-D 8 Pin Octal Socket



Boxco BC-ATS-151510 Enclosure, 150x150x100, Clear Screw Cover, ABS Plastic $17.78
ILME CHP-16LS C-Type Surface Mount Housing, Size 77.27, Lever & Cover, PG 21 $49.27
OMAL VBN-022-00 Form B Valve Connector, 10mm, 1/2" NPT, Black $2.48
Mencom VFN-029-3501 DIN Form A to M12, 5 Pole, Male Straight, Gray $30.51
Hirschmann GMN 209-12 DIN 43650 Form B 10 mm EPDM Flat Gasket $1.13
Kacon B30-21G-EG Momentary Push Button, Green, Half-Guarded $5.22
Z+F V30AE001153 Red Insulated Twin End Sleeve, 8 AWG, 1.18" Length $0.22
Menics MW86N-FF-M3 86 mm Signal Horn, 90-240V, 3 Melody, White $96.80