The Macromatic CUH20A2AF is a current sensing relay. This encapsulated relay has an input voltage of 120V AC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 2-20A and a trip time delay of 0.15-7 seconds. There is a 3 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 2-20 Amps
  • Time Trip Delay- 0.15-7 seconds
  • Sensing Time Delay on Startup- 3 Seconds
  • Input Voltage- 120V AC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 3 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH20A2AF has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

Encapsulated 120V AC Under Current Sensing Relay CUH20A2AF




Meltric 596P0N12 DS200 Metal Handle, 1-1/4" NPT Entry $509.15
Macromatic PAP480 480V Plug-in Phase Monitor Relay $55.17
ILME CAP-24LS29 C-Type Surface Mount Housing, Size 104.27, Lever & Cover, PG 29 $63.17
Meltric 596P0N10 DS200 Metal Handle, 1" NPT Entry $509.15
Saginaw SCE-10PBA Sloped Front Push Button Enclosure, 10 Position, 30.5mm $208.24
Mencom LP1-DP1-2RJ45 Low Profile Panel Interface Connector, Simplex Outlet, 2 RJ45, Single Size Housing $112.75
Macromatic PAP400 400V Plug-in Phase Monitor Relay $55.17
Deca CEP4 DIN Rail Terminal Block End Cover, For CDK 6 & CDK 10 $0.54
Saginaw SCE-806SC Screw Cover Enclosure, 8.13" x 6" x 3.5" $69.42