Home > Relays > Current Sensing Relays >

Macromatic CUH05A2AD Under Current Sensing Relay, 0.5-5A, 0.15-7 Sec, 120V, 1 Sec Delay


Macromatic CUH05A2AD Under Current Sensing Relay
Macromatic CUH05A2AD Under Current Sensing Relay, 0.5-5A, 0.15-7 Sec, 120V, 1 Sec Delay
 
Alternative Views:


Price: $87.80
Note: Please call or email [email protected] for alternatives
MFG P/N: CUH05A2AD
MFG: Macromatic
Weight (lbs): 0.3

Quantity in Stock :(Out of Stock)


Availability:
Out of Stock
Product Code: CUH05A2AD
Qty:

Description
 

The Macromatic CUH05A2AD is a current sensing relay. This encapsulated relay has an input voltage of 120V AC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 0.5-5A and a trip time delay of 0.15-7 seconds. There is a 1 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 0.5-5 Amps
  • Time Trip Delay- 0.15-7 seconds
  • Sensing Time Delay on Startup- 1 Second
  • Input Voltage- 120V AC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-25A Turns; 150A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 1 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH05A2AD has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

Macromatic 120V AC Under Current Sensing Relay CUH05A2AD




Saginaw SCE-202010ELJ Junction Enclosure, 20" x 20" x 10" $222.30
Mencom MS10SL-3MP-1M MIL-SPEC Cordset, Size 10SL-3, 3 Pole, Male Straight, 1 M $47.33
ILME MNDS-10IOA32 Kit, 10 Pole Inserts, Screw Termination, Double Lever Base, Side Entry M32 Hood $85.68
BreezEV EVC-L2-S48-25 48 Amp EV Charger, Wall Mount, 25 Foot 48A Cable $525.59
Menics MS70-Y Yellow Lens for MS70 Beacon Lights $7.21
Mencom MDE45PB-4MMP-2M Ethernet Cordset, 4 Pole, Male/Male, 2 Meter, PUR, Shielded $62.40
Sealcon CD16MR-BE M16 Dome .12" - .28" (3 - 7 mm) EMI/RFI Proof Cord Grip $15.64
ILME CKM-04N CK Series Insert, Male, Size 21.21, 4 Pin, 10A, Black $6.89
Mencom MCV-19FR-2M M23 Receptacle, 19 Pole, Female, 1/10A, 1/2" NPT, 2 Meter $101.95