Home > Relays > Current Sensing Relays >

Macromatic CUH20A2BE Under Current Sensing Relay, 2-20A, 0.5-50 Sec, 120V, 2 Sec Delay


Macromatic CUH20A2BE Under Current Sensing Relay
Macromatic CUH20A2BE Under Current Sensing Relay, 2-20A, 0.5-50 Sec, 120V, 2 Sec Delay
 
Alternative Views:


Price: $87.80
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: CUH20A2BE
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: CUH20A2BE
Qty:

Description
 

The Macromatic CUH20A2BE is a current sensing relay. This encapsulated relay has an input voltage of 120V AC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 2-20A and a trip time delay of 0.5-50 seconds. There is a 2 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 2-20 Amps
  • Time Trip Delay- 0.5-50 seconds
  • Sensing Time Delay on Startup- 2 Seconds
  • Input Voltage- 120V AC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 2 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH20A2BE has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

CUH20A2BE Encapsulated 2-20 Amp Under Current Sensing Relay




Sealcon CF17MR-BK Black M16 Flex .12" - .28" (3 - 7 mm) O.D. Cord Grip $2.26
Sealcon CD36AA-BE PG 36 Dome .87" - 1.26" (22 - 32 mm) EMI/RFI Proof Cord Grip $60.95
Sealcon CD16M1-BK Black M16 Dome 4 Hole .06" (1.4 mm) Insert Cord Grip $2.34
Jorc 2951 115V AC OPTIMUM Timer Controlled Drain, 1/4" NPT, 0-5000 PSI $454.53
Fandis FPF13KNG-100 Filter Assembly 204mm x 204mm RAL9005 - Black $19.99
Sealcon CD16MA-TE M16 Dome .16" - .31" (4 - 8 mm) O.D. Cord Grip $6.12
Macromatic SFPAD7A250 Single Channel 24V AC/DC, 1K to 250K Pump Seal Failure Relay $102.90
Mencom RJ45-M25 RJ45, M25 Port Adapter $51.17
Sealcon M16 Connector, Elongated, Male Straight, 3 Pin, 1 mm Contacts, 26-17 AWG, 5-9 mm $30.21