The Macromatic COH50A2AC is a current sensing relay. This encapsulated relay has an input voltage of 120V AC. It is designed to monitor for over current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 5-50A and a trip time delay of 0.15-7 seconds. There is no sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments.
Note: Image is an approximation. Actual part may differ.
Specifications
- Relay Function- Overcurrent
- Current Monitor Range- 5-50 Amps
- Time Trip Delay- 0.15-7 seconds
- Sensing Time Delay on Startup- None
- Input Voltage- 120V AC
- Output- 10A SPDT
- Input Voltage Tolerance- +10/-15% of nominal
- Load- 2VA
- Current Sensing- Type: Toroidal, through hole wiring
Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
Trip Point Hysteresis: -5%
- Response Time- Time Delay on Reset (Relay OFF): 100ms
Reset Time: 400ms
- Operating Temperature- -28 C to 65 C (-18 F to 149 F)
- Storage Temperature- -40 C to 85 C (-40 F to 185 F)
- Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
- Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
- Mounting- Surface mount with two #6 screws
- Termination- 0.25" male quick-connect terminals
- Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
- Approvals- UL & CUL Recognized
The relay starts monitoring for faults once the input voltage is introduced. In the event of an overcurrent situation, the AC current goes above the set Fault Trip Current for longer than the adjusted time delay. The relay energizes after the time delay on pick-up and stays energized until the current goes below the reset level. The COH50A2AC features an LED indicator which glows red to show when an overcurrent fault is detected. Has pilot duty rating. Application examples include process control, monitoring for locked rotor or load loss, or open heater or lamp.
Macromatic COH Series Relay Installation Manual
120V AC 5-50 Amp Encapsulated Over Current Sensing Relay COH50A2AC
|
|
|
|
|
|
|