Home > Relays > Current Sensing Relays >

Macromatic COH05A2AF Over Current Sensing Relay, 0.5-5A, 0.15-7 Sec, 120V, 3 Sec Delay


Macromatic COH05A2AF Over Current Sensing Relay
Macromatic COH05A2AF Over Current Sensing Relay, 0.5-5A, 0.15-7 Sec, 120V, 3 Sec Delay
 
Alternative Views:


Price: $87.80
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: COH05A2AF
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: COH05A2AF
Qty:

Description
 

The Macromatic COH05A2AF is a current sensing relay. This encapsulated relay has an input voltage of 120V AC. It is designed to monitor for over current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 0.5-5A and a trip time delay of 0.15-7 seconds. There is a 3 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Overcurrent
  • Current Monitor Range- 0.5-5 Amps
  • Time Trip Delay- 0.15-7 seconds
  • Sensing Time Delay on Startup- 3 Seconds
  • Input Voltage- 120V AC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-25A Turns; 150A Inrush for 10 Seconds
    Trip Point Hysteresis: -5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

The relay starts monitoring for faults once the input voltage is introduced and after the 3 second sensing start-up delay. In the event of an overcurrent situation, the AC current goes above the set Fault Trip Current for longer than the adjusted time delay. The relay energizes after the time delay on pick-up and stays energized until the current goes below the reset level. The COH05A2AF features an LED indicator which glows red to show when an overcurrent fault is detected. Has pilot duty rating. Application examples include process control, monitoring for locked rotor or load loss, or open heater or lamp.

Macromatic COH Series Relay Installation Manual

Macromatic 120V Over Current Sensing Relay with 3 Second Delay COH05A2AF




Menics MT5C1AL-B 1 Stack 56mm Tower Light, Blue, 24V, Steady & Flashing $44.53
Menics E08R-10R IP 67 LED Indicator, 8mm, Round Head, 110VAC, Red $7.20
Mencom MDC-5MR-M20-SC M12 5-Pole Male Receptacle, Solder Cup, M20, 4A $18.86
Cable Tie Express 8-18-N-STP 8" Natural Nylon Cable Ties with Stainless Steel Tooth, 18 lb Tensile Strength, 100 Pack $3.82
AerosUSA 1732035010 DES-PDM M50/10G Circular Cable Entry Plate, 10 Entries $16.78
Boxco BC-CGP-507018 Enclosure, 530x730x185, Solid Gray Hinged Lid, Polycarbonate $347.61
Meltric 63-14047 DSN20 20A, 277/480V, 3P+N+G Female Receptacle $128.62
Menics MS86M-F00-RBG 86mm Beacon Light, 12-24V, Red/Green/Blue $166.50
Mueller BU-21AEZ EZ Squeeze Unmarked Steel Heavy Duty Battery Clip $12.41