Home > Relays > Current Sensing Relays >

Macromatic CUH50A6AH Under Current Sensing Relay, 5-50A, 0.15-7 Sec, 12V, 5 Sec Delay


Macromatic CUH50A6AH Under Current Sensing Relay
Macromatic CUH50A6AH Under Current Sensing Relay, 5-50A, 0.15-7 Sec, 12V, 5 Sec Delay
 
Alternative Views:


Price: $84.58
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: CUH50A6AH
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: CUH50A6AH
Qty:

Description
 

The Macromatic CUH50A6AH is a current sensing relay. This encapsulated relay has an input voltage of 12V DC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 5-50A and a trip time delay of 0.15-7 seconds. There is a 5 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 5-50 Amps
  • Time Trip Delay- 0.15-7 seconds
  • Sensing Time Delay on Startup- 5 Seconds
  • Input Voltage- 12V DC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 5 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH50A6AH has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

Macromatic Under Current Sensing Relay CUH50A6AH




Mencom MIN-7MFPX-6 MIN Size II Cordset, 7 Pole, Male / Female, 18 AWG, 6 Feet $105.36
Mencom PCG-29R PG 29 0.472- 0.787" (12 - 20 mm) Cable Gland $6.72
Saginaw SCE-604FW Fiberglass Junction Enclosure w/ Window, 7.39" x 5.45" x 4.73" $243.24
Sealcon CD16NK-GY Gray 1/2" NPT Dome 1 Hole .23" (5.7 mm) Insert RJ45 Cord Grip $5.09
HTP Din 43650 Molded Form C 8 mm 3 Pole / Ground, NBR - 3 Meter $15.15
ILME MQLS-24IVA40 Kit, 24 Pole Inserts, Spring Termination, Single Lever Base, Top Entry M40 Hood $121.13
Macromatic ARP120A5 DPDT 120V Cross Wired Duplexor Alternating Relay, No Switch (5-6 Control Voltage) $50.38
Mencom CEC-M25-PA M32 to M25 Gray Plastic Reducer $6.00