Home > Relays > Current Sensing Relays >

Macromatic CUH50A8BG Under Current Sensing Relay, 5-50A, 0.5-50 Sec, 24V, 4 Sec Delay


Macromatic CUH50A8BG Under Current Sensing Relay
Macromatic CUH50A8BG Under Current Sensing Relay, 5-50A, 0.5-50 Sec, 24V, 4 Sec Delay
 
Alternative Views:


Price: $85.55
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: CUH50A8BG
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: CUH50A8BG
Qty:

Description
 

The Macromatic CUH50A8BG is a current sensing relay. This encapsulated relay has an input voltage of 24V AC/DC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 5-50A and a trip time delay of 0.5-50 seconds. There is a 4 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 5-50 Amps
  • Time Trip Delay- 0.5-50 seconds
  • Sensing Time Delay on Startup- 4 Seconds
  • Input Voltage- 24V AC/DC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 4 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH50A8BG has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

5-50 Amp Under Current Sensing Electrical Relay CUH50A8BG




Mueller BU-31602-0 Black Pressfit Insulated Banana Jack w/ Solder Pin $3.38
Boxco BC-CGS-151510 Enclosure, 150x150x100, Solid Gray Screw Cover, Polycarbonate $24.34
AerosUSA 1732033204 DES-PDM M32/4G Circular Cable Entry Plate, 4 Entries $14.62
Z+F V30AE009775 Non-Insulated End Sleeve, 1 AWG, 0.98" Length $0.21
GardTec SC120-P15/100 120mm 100 PPI Plastic Fan Filter Assembly $2.21
Lumberg Automation RKTS 5-298/5M M12 Cordset, Female Straight, 5 Pin, 5 M, Shielded $46.02
Hirschmann 942148-002 OZD Profi 12M G12 Interface Converter for Profibus Networks $1,558.73
Menics MS70S-M10-G 70mm Xenon Strobe Beacon Light, 110V, Green, Direct Mount $69.34