Home > Relays > Current Sensing Relays >

Macromatic CUH05A8AE Under Current Sensing Relay, 0.5-5A, 0.15-7 Sec, 24V, 2 Sec Delay


Macromatic CUH05A8AE Under Current Sensing Relay
Macromatic CUH05A8AE Under Current Sensing Relay, 0.5-5A, 0.15-7 Sec, 24V, 2 Sec Delay
 
Alternative Views:


Price: $85.58
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: CUH05A8AE
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: CUH05A8AE
Qty:

Description
 

The Macromatic CUH05A8AE is a current sensing relay. This encapsulated relay has an input voltage of 24V AC/DC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 0.5-5A and a trip time delay of 0.15-7 seconds. There is a 2 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 0.5-5 Amps
  • Time Trip Delay- 0.15-7 seconds
  • Sensing Time Delay on Startup- 2 Seconds
  • Input Voltage- 24V AC/DC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-25A Turns; 150A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 2 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH05A8AE has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

24V AC/DC Under Current Sensing Relay with 2 Second Startup Delay CUH05A8AE




GardTec SC92-P15/45 92mm 45 PPI Plastic Fan Filter Assembly $1.82
Sealcon CF17DR-BK Black M16 Flex .12" - .28" (3 - 7 mm) O.D. Elongated Cord Grip $2.81
Kacon KSC-5080ZAH Three Phase Solid State Relay w/ Heatsink, 220V AC Input, 90-480V AC Load, 80A $420.18
Cable Tie Express 27SC6-300-100 Heavy Duty 26" Coated Stainless Steel Cable Ties, 350 lb Tensile Strength, 100 Pack $82.95
Macromatic LCP8B100F10 24V Single Probe Liquid Level Relay, Pump Down, 4.7K to 100K, 10 Sec Delay $98.75
AerosUSA 1732014617 DES-PDM Q 17G Cable Entry Plate, 17 Cable Entries with Internal Frame $18.75
ILME MKA-V20 C-Type Metallic Hood, Size 21.21, M20, 2 Pegs $6.76
AerosUSA 1732053418 DES-PM 24/17B Cable Entry Plate, 17 Entries $13.82
Sealcon EM20MA-BK M20 Elbow Push In Conduit Fitting, Fits Size 14 $15.24