IMO UB10D2002A 2A UL 489 Circuit Breaker, 2-pole, D Curve, 10kA
2A 2-pole D-curve miniature circuit breaker with thermo-magnetic protection, 10kA breaking capacity, DIN-rail mounting, and UL 489 approval.
Why Choose the IMO UB10D2002A Circuit Breaker?
The IMO Precision Controls UB10D2002A is a 2A 2-pole miniature circuit breaker for low-current two-pole control-transformer and equipment branches that experience high inrush. It is rated for 480Y/277V AC or 96V DC and provides UL 489 branch-circuit protection in industrial control panels, machinery, and distribution equipment when applied within its electrical ratings.
Thermo-magnetic operation combines a thermal response for sustained overloads with rapid magnetic response during severe faults. The D curve delays magnetic tripping until a higher multiple of rated current, helping prevent nuisance trips on loads with brief, high startup current. A contact-position indicator provides a clear visual reference during inspection and troubleshooting.
ā” 2A Rating
Protects a correctly sized 2-pole branch circuit rated for 2A
š D Trip Curve
10ā20 Ć In magnetic range supports loads with high startup current
š”ļø 10kA Capacity
Provides 10kA short-circuit breaking capacity for suitable electrical systems
ā
UL 489 Approved
Approved for branch-circuit protection when selected and installed correctly
ā ļø Coordinate the 2A 2-pole Breaker with the Load
Confirm the 2A rating, 2-pole configuration, conductor current, 480Y/277V AC or 96V DC rating, available fault current, D trip curve, ambient conditions, and equipment requirements before installation. A D-curve breaker does not replace separate motor-overload protection when the equipment or applicable code requires it.
š 2A D-Curve Magnetic Trip Range
The D-curve magnetic element operates at 10ā20 times rated current. For the UB10D2002A, this corresponds to an instantaneous magnetic range of approximately 20ā40A. The thermal element responds to sustained overloads. Confirm coordination with normal startup current and upstream or downstream protective devices.
Key Features & Benefits
- 2-pole DIN-rail mounting configuration
- Rated for 480Y/277V AC or 96V DC
- Approximate magnetic trip range of 20ā40A
- Thermo-magnetic overload and short-circuit protection
- Contact-position indicator for visual status checks
- 18ā3 AWG conductor range with 2.5 Nm fastening torque
- UL 489, IEC 60947-2, IEC 60898-1, and RoHS compliance
Technical Specifications
| Dimensions |
4.25" Length x 1.38" Width x 2.64" Depth (108mm x 35mm x 67mm) |
| Rated Current |
2 Amp |
| Voltage Rating |
480Y / 277V AC / 96V DC |
| Number of Poles |
2 |
| Tripping Curve |
D (10-20 In) |
| Calibration Temperature |
104 F (40 C) |
| Operating Temperature |
-13 F to 131 F (-25 C to 55 C) |
| Rated Operational Frequency |
50/60 Hz |
| Short Circuit Breaking Capacity |
10kA |
| Lifespan |
20,000 Operations (Mechanical), 6000 Operations (Electrical) |
| Vibration Resistance |
+/- 1mm @ 5-25 Hz; 50 m/s² @ 25-150 Hz |
| Fastening Torque |
2.5 Nm (22.2 lb/in) |
| Wire Range |
18-3 AWG |
| NEMA Rating |
NEMA 1 (IP20 - Protection from objects 12.5 mm (0.5") in diameter or greater) |
| Approvals |
UL 489, IEC 60947-2 & IEC 60898-1, RoHS Compliant |
š 2-pole Breaker Selection and Installation Overview
1. Calculate the Load: Confirm that conductor current and connected equipment are compatible with a 2A protective device.
2. Verify Pole and Voltage Requirements: Confirm that the circuit requires 2 poles and operates within the 480Y/277V AC or 96V DC rating.
3. Check Fault and Inrush Current: Verify the available fault current, 10kA breaking capacity, and compatibility of the D curve with normal startup demand.
4. Mount and Terminate: Install on DIN rail using conductors within the specified 18ā3 AWG range and apply the listed 2.5 Nm terminal torque.
5. Inspect Before Energizing: Verify wiring, labeling, protective-device coordination, and code compliance before commissioning.
Circuit-breaker selection and installation must be completed by qualified personnel in accordance with the equipment documentation and applicable electrical codes.
š Typical Uses for the 2A 2-pole D-Curve Breaker
⢠Two-pole control-transformer circuits ⢠Low-current inductive equipment branches ⢠Machine-control loads with high startup current ⢠AC or DC circuits requiring 2A two-pole D-curve protection
|
|
 |
 |
 |
 |

|