Macromatic THR-16561-34 Encapsulated Time Delay Relay, Delayed Interval, 240V, 0.1-10 Hr


Macromatic THR-16561-34 Time Delay Relay
Macromatic THR-16561-34 Encapsulated Time Delay Relay, Delayed Interval, 240V, 0.1-10 Hr
 
Alternative Views:


Price: $33.03
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: THR-16561-34
MFG: Macromatic
Weight (lbs): 0.5



Availability:
In Stock
Product Code: THR-16561-34
Qty:

Description
 

The Macromatic THR-16561-34 is a triggered delayed interval Time Delay Relay. This encapsulated relay has an input voltage of 240V AC. It has an adjustable time range of 0.1 to 10 hours. Time is adjusted by turning the blue dial at the top. The encasement of the unit is made for use under harsh conditions. The design is microprocessor-based to provide better functionality, and is perfect for high volume OEM applications. Note: Image is for reference, actual part may differ

Specifications

  • Relay Function- Triggered Delayed Interval
  • Mounting Style- Surface Mount with #8 or #10 Screw
  • Termination- 0.25" Male Quick Connect Terminals
  • Relay Timing Range- 0.1 - 10 Hrs
  • Input Voltage- 240V AC
  • Output- 10 Amps SPDT
  • Voltage Tolerance- AC Operation: +10/-15% of nominal at 50/60 Hz. DC Operation: +10/-15% of nominal voltage
  • Load- Max. 2VA
  • Setting Accuracy- Maximum Setting (Adjustable): +5%, -0% Minimum Setting (Adjustable): +0%, -50% Fixed Time Delay: +/-2% or 50ms, whichever is greater
  • Repeat Accuracy- The greater amount of +/- 0.1% or +/- 0.04 Sec
  • Reset Time- 40ms
  • Startup Time- 0.05 seconds
  • Maintain Function Time- 0.01 seconds
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -45 C to 85 C (-49 F to 185 F);
  • Output Contacts- 10A @ 240VAC / 7A @ 28VDC SPDT, 1/4 hp @ 120VAC (N.O.)
  • Life- Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Overall Dimensions- 2" Height x 2" Width x 1.14" Depth
  • Approvals- C UR US, CE

With Delayed Interval, the relay can accept a trigger after the input voltage is introduced. Once the trigger is introduced, the (t1) time delay starts. After that, the (t2) time delay starts and the relay is energized for the duration of the time delay. When the (t2) time delay finishes, the relay de-energizes. The trigger then needs to be re-applied for the cycle to start again.

Macromatic THR Series Relay Installation Instructions

Explanation of Macromatic Time Delay Relay Timing Functions




AerosUSA 1732034008 DES-PDM M40/8G Circular Cable Entry Plate, 8 Entries $15.98
Menics MS70LT-MFFF-Y 70mm LED Beacon Light, 110-220V, Yellow, Flashing, Direct Mount $83.25
Hirschmann 933139100 ELKA 4012 M12 Cable Socket, PG 7, 4 Pin, Female $13.50
Mencom MDC-5MR-PG9 M12 Receptacle, 5 Pole, Male Straight, 4A, PG 9 $14.83
Kacon HR710-4PL-24VDC Electro Mechanical Relay, 4PDT, 24V DC, 10A $18.05
Menics MS86L-B02-Y 86mm Beacon Light, 24V, Yellow, w/ Alarm $77.44
Meltric 33-38165 DS30 Male Inlet, 30A 120V, 1P+N+G $172.91
Qronz TL70BK-NR-QD24 70 mm 1 Stack LED Tower Light, Red, Quick Disconnect, 24V, Diffused Lens $49.56
Kacon K16-S113 Soldering Socket for K16 Series $4.58