Home > Relays > Current Sensing Relays >

Macromatic CUH20A2AF Under Current Sensing Relay, 2-20A, 0.15-7 Sec, 120V, 3 Sec Delay


Macromatic CUH20A2AF Under Current Sensing Relay
Macromatic CUH20A2AF Under Current Sensing Relay, 2-20A, 0.15-7 Sec, 120V, 3 Sec Delay
 
Alternative Views:


Price: $87.80
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: CUH20A2AF
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: CUH20A2AF
Qty:

Description
 

The Macromatic CUH20A2AF is a current sensing relay. This encapsulated relay has an input voltage of 120V AC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 2-20A and a trip time delay of 0.15-7 seconds. There is a 3 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 2-20 Amps
  • Time Trip Delay- 0.15-7 seconds
  • Sensing Time Delay on Startup- 3 Seconds
  • Input Voltage- 120V AC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 3 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH20A2AF has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

Encapsulated 120V AC Under Current Sensing Relay CUH20A2AF




ILME CSHF-10 CSH Series Insert, Female, Size 57.27, 10 Pin, 16A $15.50
Saginaw SCE-121010SC Screw Cover Enclosure, 12.13" x 10" x 10"" $165.25
Jorc 2503 230V AC COMBO Timer Controlled Drain, Dual Inlet, 0-230 PSI $170.88
Menics PWEC-1FF-G 1 Stack LED Tower Light, Green, Steady, 90-240V $124.13
HTP 12FA4A10 M12 Molded Cable, 10M, Female Right Angle Connector, 4-Pin $27.99
Meltric 63-84142 DSN100 100A, 600V, 2P+G Female Receptacle $617.55
ILME CDM-40 CD Series Insert, Male, Size 77.27, 40 Pin, 10A $16.55
Hirschmann Din 43650 Form A PG 9, 110-120V LED, MOV Suppression - NBR Flat $8.15
Z+F V30AE004157 Pink Polypropylene Insulated End Sleeve, 22 AWG, 0.63" Length $0.03