The Macromatic LCP8B100F3 is a single probe pump down (drain) liquid level control relay. This 8 Pin plug-in relay has an input voltage of 24V AC. It monitors the level of conductive liquid (such as tap water, chemical solution, seawater, etc.) in a tank. Sensitivity is adjustable within the set range. Used to monitor liquid levels in the tank for pumps, solenoids, or valves. Electroplating is prevented due to the DC voltage pulsed through the probe, while the fixed time delay prevents rapid cycling. Pilot duty rating. Note: LCP2B250F2 pictured for reference.

Specifications

  • Relay Function- Single Probe Pump Down Liquid Level Control Relay
  • Input Voltage- 24V AC
  • Output- 10A SPDT
  • Sensitivity Range- 4.7K to 100K Ohms
  • Voltage Tolerance- AC Operation: +10 / -15% of nominal at 50/60 Hz
  • Load- 2 VA
  • Probe Voltage- 5V DC Pulsed
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10A @ 240V AC / 7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
  • Life- Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Response Time- Pick Up: 3 Seconds, Drop Out: 500 Milliseconds
  • Dimensions- 2.4" Height x 1.7" Width x 3.2" Depth
  • Approvals- UL and CUL recognized, UL & CUL listed (with Socket)

When the level of conductive liquid goes above the probe, the fixed time delay starts and the LED flashes red. The relay energizes after the time delay and the LED is solid red. It stays this way until the liquid drains below the level of the probe. The relay is then no longer energized and the LED is green.

Liquid Level Relay Connection Diagram

Macromatic LCP Series Installation Instructions

Macromatic Pump Down Liquid Level Control Relay with 3 Second Delay LCP8B100F3


Related Products
Macromatic 70169-D 8 Pin Octal Socket
Price: $5.04

Add
Macromatic 70169-D 8 Pin Octal Socket



Meltric 596P0N12 DS200 Metal Handle, 1-1/4" NPT Entry $509.15
ILME CDMD-0.3 Male Crimp Pin, CD Series, Gold Plated, 10A, 22-26 AWG $2.18
Menics MT4B2AL-RG 2 Stack 45mm Tower Light, Red Green, 24V $29.22
AerosUSA 1731020105 SPP 5G Insert for Cable Entry Frame, 1 Hole, 0.2-0.24", Set of 10 $22.41
ILME CAP-24CS229 C-Type Surface Mount Housing, Size 104.27, 4 Pegs & Cover, 2 PG 29 Entries $55.86
HTP 310 DIN 43650 Form C Nitrile Profile Gasket $5.46
Mueller BU-60PR2 Phone Tip Alligator Clip $0.89
Light Efficient Design LED-7313-FC-G4 3.5W, G23 LED PL Light, 2700-4000K, 120-277V, 2 Pin $8.25
Mencom LP1-4RJ45 Low Profile Panel Interface Connector, 4 RJ45, Single Size Housing $93.55