The Macromatic CUH05A8BH is a current sensing relay. This encapsulated relay has an input voltage of 24V AC/DC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 0.5-5A and a trip time delay of 0.5-50 seconds. There is a 5 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 0.5-5 Amps
  • Time Trip Delay- 0.5-50 seconds
  • Sensing Time Delay on Startup- 5 Seconds
  • Input Voltage- 24V AC/DC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-25A Turns; 150A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 5 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH05A8BH has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

Under Current Sensing Relay with 5 Second Startup Delay CUH05A8BH




Hirschmann 934888034 GDM Form A Solenoid Valve Connector, M16, 24V LED, MOV Suppression - NBR Profile $9.77
Euri Lighting EA19-9W5000CEC-2 9W A19 LED Light, 3000K, Set of 2 $6.39
Sealcon CD12MA-BR Nickel Plated Brass M12 Dome .12" - .26" (3 - 6.5 mm) O.D. Cord Grip $5.60
Meltric 595P0N15 DSN150 1-1/2" NPT Metal Handle $175.64
ILME CZAV-25L216 C-Type Metallic Hood, Size 66.16, PG 16, 2 Pegs, 2 Top Entries $41.29
Mencom MDC-4MR-M20 M12 Receptacle, 4 Pole, Male Straight, 4A, M20 $14.30
HTP Din 43650 Form B, 24V LED, MOV Suppression, 11mm, NBR - 5 M $23.95
Seifert 4732902003 Filter Assembly 325mm x 325mm Black $52.45
Sealcon NM-25-SS M25 Locking Nut $25.37