Macromatic PMPU Phase Monitor Relay Competitive Comparison THREE-PHASE MOTOR PROTECTION Macromatic PMPU Phase Monitor Relay ComparisonCompare the Macromatic PMPU with Symcom 201A-AU, SSAC PLMU11 and Diversified SLU-100-ASA relays. Review voltage coverage, reset options and output ratings to choose a three-phase monitor for your control panel. The Macromatic PMPU monitors three-phase power for phase loss, phase reversal, voltage unbalance, undervoltage and overvoltage. Its adjustable undervoltage threshold helps match protection to equipment requirements, while an external manual-reset option lets operators acknowledge a cleared fault before the relay resets.
190–500V ACNominal voltage coverageTwo setting scales: 190–250V and 380–500V.
80–95%Adjustable undervoltage tripPercentage of the selected line voltage.
External resetOperator-controlled resetOptional normally closed momentary switch.
Phase Monitor Relay Feature ComparisonSeparate voltage models are not additional voltage settings on the standard PMPU. Check the exact part number and current documentation before specifying a replacement. What the PMPU Adjustments DoUndervoltage: 80–95%Select the low-voltage trip point to suit the equipment. For example, a 90% setting on a 480V system equals a 432V undervoltage threshold. Trip delay: 0.3–30 secondsAdjust the delay for undervoltage, overvoltage and unbalance faults. Phase loss and reversal use a separate, fixed 100 ms response. Restart: 1–300 secondsIn automatic-reset mode, delay re-energization after a fault clears. Manual-reset mode requires the external reset switch and does not use this delay. Before Replacing a Three-Phase Monitor Relay
PMPU Phase Monitor QuestionsDoes PMPU continue monitoring after a phase is lost?Yes. PMPU retains fault indication and continues voltage monitoring with a lost phase. This describes the monitor’s operation, not permission for the motor to keep running under a phase-loss condition. Can PMPU replace a competing phase monitor?PMPU is a replacement candidate when its voltage coverage, protection functions and output ratings fit the application. Confirm socket pin assignments and reset wiring before treating any model as interchangeable. |