Home > Relays > Liquid Level Control Relays >

Macromatic LCP2A100F15 120V Single Probe Liquid Level Relay, Pump Up, 4.7K to 100K, 15 Sec Delay


Macromatic 120V Single Probe Liquid Level Relay, Pump Up, 4.7K to 100K, 15 Sec
Macromatic LCP2A100F15 120V Single Probe Liquid Level Relay, Pump Up, 4.7K to 100K, 15 Sec Delay
 
Alternative Views:


Price: $90.38
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: LCP2A100F15
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: LCP2A100F15
Qty:

Description
 

The Macromatic LCP2A100F15 is a single probe pump up (fill) liquid level control relay. This 8 Pin plug-in relay has an input voltage of 120V AC. It monitors the level of conductive liquid (such as tap water, chemical solution, seawater, etc.) in a tank. Sensitivity is adjustable within the set range. Used to monitor liquid levels in the tank for pumps, solenoids, or valves. Electroplating is prevented due to the DC voltage pulsed through the probe, while the fixed time delay prevents rapid cycling. Pilot duty rating. Note: LCP2B250F2 pictured for reference.

Specifications

  • Relay Function- Single Probe Pump Up Liquid Level Control Relay
  • Input Voltage- 120V AC
  • Output- 10A SPDT
  • Sensitivity Range- 4.7K to 100K Ohms
  • Voltage Tolerance- AC Operation: +10 / -15% of nominal at 50/60 Hz
  • Load- 2 VA
  • Probe Voltage- 5V DC Pulsed
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10A @ 240V AC / 7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
  • Life- Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Response Time- Pick Up: 15 Seconds, Drop Out: 500 Milliseconds
  • Dimensions- 2.4" Height x 1.7" Width x 3.2" Depth
  • Approvals- UL and CUL recognized, UL & CUL listed (with Socket)

When the level of conductive liquid goes below the probe, the fixed time delay starts and the LED flashes red. The relay energizes after the time delay and the LED is solid red. It stays this way until the liquid comes back up to the probe. The relay is then no longer energized and the LED is green.

Liquid Level Relay Connection Diagram

Macromatic LCP Series Installation Instructions

Macromatic Single Probe Pump Up Liquid Level Control Relay LCP2A100F15


Related Products
Macromatic 70169-D 8 Pin Octal Socket
Price: $5.04

Add
Macromatic 70169-D 8 Pin Octal Socket



Red Lion N-Tron 716TX 16 Port Managed Ethernet Switch $1,824.36
Mencom CRB-M32PASW M32 Cable Gland Plug, Black Plastic, w/ Gasket $2.26
Sealcon CD07CR-BE PG 7 / 1/4" NPT Dome .08" - .20" (2 - 5 mm) EMI/RFI Proof Elongated Cord Grip $14.51
Menics MAM-B070D Plastic Base for Tower Lights w/ Gasket, 70mm Diameter $4.22
Menics MT8C2CL-RY 2 Stack 85mm Tower Light, Red Yellow, 220-240V, Steady & Flashing $72.51
Macromatic CUH50A6BG Under Current Sensing Relay, 5-50A, 0.5-50 Sec, 12V, 4 Sec Delay $84.58
Mencom MIN-6MR-1 MIN Size I Receptacle, 6 Pole, Male, 8A, 1/2"-NPT $20.16
Lumberg Automation RSU 19-RKWU 19-242/5M M23 Cordset, Male Straight / Female Right Angle, 19 Pin, 5 M $216.68
Mencom CRB-M25PASW M25 Cable Gland Plug, Black Plastic, w/ Gasket $1.87