Macromatic Isolated Output 3 Phase Monitor Relay Competitive Comparison

THREE-PHASE POWER MONITORING

Macromatic Isolated Output 3 Phase Monitor Relay Comparison

Compare Macromatic PJPU-FA8X and PMPU-FA8X with MPE 001-DVM-118-U and 001-DVM-118-OV phase monitor relays. Review protection thresholds, response times and isolated output ratings for motor control panels and alarm circuits.

Both Macromatic models use True RMS voltage sensing and retain fault indication during phase loss. The key choice is fault response: PJPU-FA8X indicates phase unbalance without tripping; PMPU-FA8X adds unbalance tripping and overvoltage protection.

100 ms
Phase loss / reversal

Macromatic dropout response

2 seconds
Restart delay

At power-up and after fault correction

3.0 inches
Macromatic relay height

Compared with 3.75 inches for MPE

Choose the Macromatic model for your application

Macromatic PJPU-FA8X

Choose this model when phase loss, phase reversal and undervoltage should trip the relay, but 6% phase unbalance should provide an indication only. It does not include overvoltage protection.

Shop PJPU-FA8X →

Macromatic PMPU-FA8X

Choose this model when the relay must also trip for phase unbalance and overvoltage. Its fixed overvoltage threshold is 10% above the line voltage setting.

Shop PMPU-FA8X →

Isolated output phase monitor relay specifications

Values apply to both models in each column unless a model is specified. Voltage percentages refer to the selected nominal line voltage.

Feature Macromatic
PJPU-FA8X
PMPU-FA8X
MPE
001-DVM-118-U
001-DVM-118-OV
Voltage & protection
Nominal voltage range Macromatic PJPU-FA8X / PMPU-FA8X190–500 VAC, 50/60 Hz
Dial scales: 190–250 V and 380–500 V
MPE 001-DVM-118-U / 001-DVM-118-OV200–525 VAC, 50/60 Hz
Dial scales: 200–280 V and 425–525 V
Phase loss Macromatic PJPU-FA8X / PMPU-FA8XYes MPE 001-DVM-118-U / 001-DVM-118-OVYes
Phase reversal Macromatic PJPU-FA8X / PMPU-FA8XYes MPE 001-DVM-118-U / 001-DVM-118-OVYes
Undervoltage Macromatic PJPU-FA8X / PMPU-FA8XFixed at −10% MPE 001-DVM-118-U / 001-DVM-118-OVFixed at −15% for 200–280 V
Fixed at −10% for 425–525 V
Phase unbalance Macromatic PJPU-FA8X / PMPU-FA8XFixed at 6%
PJPU-FA8X: indication only
PMPU-FA8X: indication and relay trip
MPE 001-DVM-118-U / 001-DVM-118-OVFixed at 6%
001-DVM-118-U: indication only
001-DVM-118-OV: indication and relay trip
Overvoltage Macromatic PJPU-FA8X / PMPU-FA8XPJPU-FA8X: no
PMPU-FA8X: yes, fixed at +10%
MPE 001-DVM-118-U / 001-DVM-118-OV001-DVM-118-U: no
001-DVM-118-OV: yes; +15% for 200–280 V, +10% for 425–525 V
Dropout timing
Phase loss & reversal Macromatic PJPU-FA8X / PMPU-FA8X100 milliseconds (0.1 second) MPE 001-DVM-118-U / 001-DVM-118-OV1 second
Phase unbalance Macromatic PJPU-FA8X / PMPU-FA8XPJPU-FA8X: no trip
PMPU-FA8X: 4 seconds; 0.25 second for severe unbalance above 12%
MPE 001-DVM-118-U / 001-DVM-118-OV001-DVM-118-U: no trip
001-DVM-118-OV: 5 seconds
Undervoltage Macromatic PJPU-FA8X / PMPU-FA8X4 seconds MPE 001-DVM-118-U / 001-DVM-118-OV5 seconds
Restart & reset
Power-up delay Macromatic PJPU-FA8X / PMPU-FA8X2 seconds MPE 001-DVM-118-U / 001-DVM-118-OV2 seconds
Restart after a fault Macromatic PJPU-FA8X / PMPU-FA8X2 seconds after fault correction MPE 001-DVM-118-U / 001-DVM-118-OV2 seconds after fault correction
Reset Macromatic PJPU-FA8X / PMPU-FA8XAutomatic MPE 001-DVM-118-U / 001-DVM-118-OVAutomatic
Output, installation & indication
Relay output Macromatic PJPU-FA8X / PMPU-FA8XSPDT + SPNO
5 A at 277 VAC / 5 A at 30 VDC
1/3 hp at 120/240 VAC; B300
MPE 001-DVM-118-U / 001-DVM-118-OVSPDT + SPNO
10 A resistive at 240 VAC
Mounting Macromatic PJPU-FA8X / PMPU-FA8X8-pin octal plug-in MPE 001-DVM-118-U / 001-DVM-118-OV8-pin octal plug-in
Adjustment knob Macromatic PJPU-FA8X / PMPU-FA8XLine-to-line voltage MPE 001-DVM-118-U / 001-DVM-118-OVNominal voltage
Status LED Macromatic PJPU-FA8X / PMPU-FA8XTwo-color: red and green MPE 001-DVM-118-U / 001-DVM-118-OVRed
Dimensions (W × D × H) Macromatic PJPU-FA8X / PMPU-FA8X1.75 × 2.38 × 3.0 inches MPE 001-DVM-118-U / 001-DVM-118-OV1.75 × 2.38 × 3.75 inches
Approvals Macromatic PJPU-FA8X / PMPU-FA8XUL & cUL Recognized; CE
UL & cUL Listed with appropriate socket
MPE 001-DVM-118-U / 001-DVM-118-OVUL & cUL Recognized
UL & cUL Listed with appropriate socket

Before selecting a replacement: Check the voltage dial scale, socket wiring, contact load rating and required fault response. A shared 8-pin base does not establish interchangeability. Macromatic applications above 300 V require a 600 V-rated socket, such as 70169-D.

What the differences mean for your control panel

Faster response to phase faults. Macromatic's 0.1-second phase loss and reversal delay is one-tenth of the listed MPE delay. Evaluate the response time alongside the protection requirements of the connected equipment.

Less relay height. The Macromatic housing is 0.75 inch shorter. Allows additional space for the socket, wiring and installation clearance.

Separate alarm contact. The SPDT + SPNO configuration provides an isolated contact for an alarm circuit. Compare the complete wiring diagram and load category; the MPE 10 A resistive rating and Macromatic horsepower or pilot-duty ratings describe different loads.

Common selection questions

Does PJPU-FA8X trip on phase unbalance?

No. It indicates a 6% unbalance condition without tripping. Choose PMPU-FA8X when phase unbalance must de-energize the relay.

Which model includes overvoltage protection?

PMPU-FA8X trips at 10% above the selected line voltage, with a 4-second overvoltage dropout delay. PJPU-FA8X does not provide overvoltage protection.

Does phase loss stop Macromatic fault monitoring?

These models continue voltage monitoring and retain fault indication during a lost phase. This allows the fault condition to remain visible during troubleshooting.

Need help matching a phase monitor relay?

Email your existing part number, system voltage and required fault response to [email protected].

Last reviewed September 21, 2026. Verify the exact relay specifications on the product page before ordering.