Home > Relays > Current Sensing Relays >

Macromatic CUH50A6AC Under Current Sensing Relay, 5-50A, 0.15-7 Sec, 12V


Macromatic CUH50A6AC Under Current Sensing Relay
Macromatic CUH50A6AC Under Current Sensing Relay, 5-50A, 0.15-7 Sec, 12V
 
Alternative Views:


Price: $84.58
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: CUH50A6AC
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: CUH50A6AC
Qty:

Description
 

The Macromatic CUH50A6AC is a current sensing relay. This encapsulated relay has an input voltage of 12V DC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 5-50A and a trip time delay of 0.15-7 seconds. There is no sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 5-50 Amps
  • Time Trip Delay- 0.15-7 seconds
  • Sensing Time Delay on Startup- None
  • Input Voltage- 12V DC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH50A6AC has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

12V DC Encapsulated Under Current Sensing Relay CUH50A6AC




Sealcon Straight Female Thread M23 Signal Connector, 7 Pole $17.93
Deca CTR4 Screw Clamp Disconnect DIN Rail Terminal Block, 2 Poles, 10-22 AWG $1.79
ILME CHP-16CS C-Type Surface Mount Housing, Size 77.27, 4 Pegs & Cover, PG 21 $41.83
Mencom PCG-07R-B PG 7 0.079-0.196 (2 - 5mm) Cable Gland $2.16
Mencom MDC-CAP Cap for M12 MDC Series Male Threads $6.53
Sealcon CD63MP-BK Black M63 Dome Solid Insert Cord Grip $39.36
Saginaw SCE-604SC Screw Cover Enclosure, 6.13" x 4" x 3" $58.94
Saginaw SCE-806SC Screw Cover Enclosure, 8.13" x 6" x 3.5" $72.82
Sealcon CD22MP-BK Black M20 Dome Solid Insert Cord Grip, 1.1" Length $4.44