Home > Relays > Liquid Level Control Relays >

Macromatic LCP2B100F2 120V Single Probe Liquid Level Relay, Pump Down, 4.7K to 100K, 2 Sec Delay


Macromatic 120V Single Probe Liquid Level Relay, Pump Down, 4.7K to 100K, 2 Sec
Macromatic LCP2B100F2 120V Single Probe Liquid Level Relay, Pump Down, 4.7K to 100K, 2 Sec Delay
 
Alternative Views:


Price: $90.38
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: LCP2B100F2
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: LCP2B100F2
Qty:

Description
 

The Macromatic LCP2B100F2 is a single probe pump down (drain) liquid level control relay. This 8 Pin plug-in relay has an input voltage of 120V AC. It monitors the level of conductive liquid (such as tap water, chemical solution, seawater, etc.) in a tank. Sensitivity is adjustable within the set range. Used to monitor liquid levels in the tank for pumps, solenoids, or valves. Electroplating is prevented due to the DC voltage pulsed through the probe, while the fixed time delay prevents rapid cycling. Pilot duty rating. Note: LCP2B250F2 pictured for reference.

Specifications

  • Relay Function- Single Probe Pump Down Liquid Level Control Relay
  • Input Voltage- 120V AC
  • Output- 10A SPDT
  • Sensitivity Range- 4.7K to 100K Ohms
  • Voltage Tolerance- AC Operation: +10 / -15% of nominal at 50/60 Hz
  • Load- 2 VA
  • Probe Voltage- 5V DC Pulsed
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10A @ 240V AC / 7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
  • Life- Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Response Time- Pick Up: 2 Seconds, Drop Out: 500 Milliseconds
  • Dimensions- 2.4" Height x 1.7" Width x 3.2" Depth
  • Approvals- UL and CUL recognized, UL & CUL listed (with Socket)

When the level of conductive liquid goes above the probe, the fixed time delay starts and the LED flashes red. The relay energizes after the time delay and the LED is solid red. It stays this way until the liquid drains below the level of the probe. The relay is then no longer energized and the LED is green.

Liquid Level Relay Connection Diagram

Macromatic LCP Series Installation Instructions

Macromatic Pump Down Liquid Level Control Relay with 2 Second Delay LCP2B100F2


Related Products
Macromatic 70169-D 8 Pin Octal Socket
Price: $5.04

Add
Macromatic 70169-D 8 Pin Octal Socket



ILME CDDF-108N CDD Series Insert, Female, Size 104.27, 108 Pin (109-216) $19.28
Macromatic SFP024C100 Dual Channel 24V, 4.7K to 100K Pump Seal Failure Relay $78.29
Meltric 592M0 DSN30 Metal Straight Angle Adapter $68.09
Meltric 596P0N10 DS200 Metal Handle, 1" NPT Entry $509.15
Deca CTR4 Screw Clamp Disconnect DIN Rail Terminal Block, 2 Poles, 10-22 AWG $1.79
Jorc 2663 24V AC OPTIMUM Timer Controlled Drain, 1/2" NPT, 0-230 PSI $161.60
Sealcon CD20MS-06 Gray M20 Dome .28" x .47" (7 x 12 mm) Romex Cord Grip $3.92
Red Lion N-Tron 306FX2-SC Industrial Ethernet Switch, 6-Port, Multimode SC Fiber, 2KM Range $958.04
Sealcon OR-38-VT 3/8" NPT Viton O-Ring $3.09