Home > Relays > Current Sensing Relays >

Macromatic CUH50A2AD Under Current Sensing Relay, 5-50A, 0.15-7 Sec, 120V, 1 Sec Delay


Macromatic CUH50A2AD Under Current Sensing Relay
Macromatic CUH50A2AD Under Current Sensing Relay, 5-50A, 0.15-7 Sec, 120V, 1 Sec Delay
 
Alternative Views:


Price: $87.79
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: CUH50A2AD
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: CUH50A2AD
Qty:

Description
 

The Macromatic CUH50A2AD is a current sensing relay. This encapsulated relay has an input voltage of 120V AC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 5-50A and a trip time delay of 0.15-7 seconds. There is a 1 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 5-50 Amps
  • Time Trip Delay- 0.15-7 seconds
  • Sensing Time Delay on Startup- 1 Second
  • Input Voltage- 120V AC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 1 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH50A2AD has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

CUH50A2AD Under Current Sensing Electrical Relay




Mencom 2M20MPOT M20 Lock Nut, Nickel Plated Brass, w/ Cutting Edge $8.45
ILME CMP-03.2 830V Surface Mount Housing, Size 57.27, Double Lever, PG 16 $57.92
Kacon KLLAL2 Medium Duty Limit Switch, Snap Action Roller Lever, 1NO 1NC Contacts $31.98
Mencom LP1-2USB-BFAF Low Profile Panel Interface Connector, 2 USB, Single Size Housing $129.55
ILME CIF-2.4 PCB Mount Female Insert $9.83
Lumberg Automation RKMV 4-07/5M, Female Straight, 4 Pin, 5 M, M8 Molded Cable $23.06
ILME CDDF-24 CDD Series Insert, Female, Size 44.27, 24 Pin, 10A $12.01
Sealcon CD16AS-03 Black PG 16 Dome .20" x .45" (5 x 11.5 mm) Romex Cord Grip $5.31