Home > Relays > Current Sensing Relays >

Macromatic CUH50A6AG Under Current Sensing Relay, 5-50A, 0.15-7 Sec, 12V, 4 Sec Delay


Macromatic CUH50A6AG Under Current Sensing Relay
Macromatic CUH50A6AG Under Current Sensing Relay, 5-50A, 0.15-7 Sec, 12V, 4 Sec Delay
 
Alternative Views:


Price: $84.58
Note: Ships in 10-15 Business Days. Contact us to confirm current ship date
MFG P/N: CUH50A6AG
MFG: Macromatic
Weight (lbs): 0.3



Availability:
In Stock
Product Code: CUH50A6AG
Qty:

Description
 

The Macromatic CUH50A6AG is a current sensing relay. This encapsulated relay has an input voltage of 12V DC. It is designed to monitor for under current faults and has an output of 10A SPDT. It checks AC current, with an adjustable range of 5-50A and a trip time delay of 0.15-7 seconds. There is a 4 second sensing time delay on startup. The built-in current transformer promotes easy access and greater sensitivity. The encapsulated casing is ideal for harsh environments. Note: Image is an approximation. Actual part may differ.

Specifications

  • Relay Function- Under Current
  • Current Monitor Range- 5-50 Amps
  • Time Trip Delay- 0.15-7 seconds
  • Sensing Time Delay on Startup- 4 Seconds
  • Input Voltage- 12V DC
  • Output- 10A SPDT
  • Input Voltage Tolerance- +10/-15% of nominal
  • Load- 2VA
  • Current Sensing- Type: Toroidal, through hole wiring
    Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
    Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
    Trip Point Hysteresis: +5%
  • Response Time- Time Delay on Reset (Relay OFF): 100ms
    Reset Time: 400ms
  • Operating Temperature- -28 C to 65 C (-18 F to 149 F)
  • Storage Temperature- -40 C to 85 C (-40 F to 185 F)
  • Output Contacts- 10 Amperes @ 240VAC, General Purpose; 8 Amperes @ 28VDC, Resistive; 1/4HP @ 120/240VAC; B300
  • Life- Mechanical: 10,000,000 Operations, Full Load: 100,000 Operations
  • Mounting- Surface mount with two #6 screws
  • Termination- 0.25" male quick-connect terminals
  • Overall Dimensions- 3.5" Height x 2.5" Width x 1.5" Depth
  • Approvals- UL & CUL Recognized

When the input voltage is introduced, and after the 4 second start-up delay, the relay then starts monitoring for faults. For an undercurrent situation, the current needs to go under the set Fault Trip Current for longer than the time delay. The relay energizes after the time delay and will de-energize once the current goes over the reset level. The CUH50A6AG has an LED indicator which glows red to show if an undercurrent fault is detected. Has pilot duty rating. Applications such as process control, monitoring for locked rotor or load loss, and open heater or lamp are all suited for this type of relay.

Macromatic CUH Series Relay Installation Manual

Under Current Sensing Relay with Encapsulated Housing CUH50A6AG




Mencom 242PA/SW PG 42 Lock Nut, Black $3.36
Sealcon CD12MA-SS M12 Dome .12" - .26" (3 - 6.5 mm) O.D. Cord Grip w/ NBR Insert $40.32
Mencom MDE45-4FR-RJ45-BM-2M Ethernet Receptacle, 4 Pole, Female, PG 9, 2 M $40.32
Kacon T22-271GD4 22 mm Green Momentary Push Button, SPDT, 24V DC LED $32.64
Saginaw SCE-1212SC Screw Cover Enclosure, 12.13" x 12" x 6"" $133.49
Deca DIN Rail Terminal Block End Plate, For 40 x 74 mm Blocks $0.65
Macromatic LCP8B100F5 24V Single Probe Liquid Level Relay, Pump Down, 4.7K to 100K, 5 Sec Delay $98.75
Mencom PBEC-3MFP-5M Profibus DP Cordset, 3 Pole, Male/Female Straight, 5 M $90.34