The Red Lion C48CD105 C48 series panel meter is a standard dual preset counter with dual NPN OC outputs. It has a 2 line, 6 digit, transmissive LCD display with backlighting and a 1/16 DIN housing. The backlit display shows a red digital readout on the main line and a green readout on the lower line. It resists noise interference, making it perfect for industrial applications. AC powered.
Features
- Two Presets
- Bi-directional & Quadrature Counting
- Dual Line, 6 Digit Transmissive LCD Display w/Backlighting
- Red Top Line & Green Lower Line
- Dual NPN OC Outputs
- Up to 11KHz
- NEMA 4X/IP65 - Front Panel
- RS-485 Communications Capability
- Status Indicators for Outputs
- Programmable User Inputs
- Function Keys on Front Panel
- Lightweight Housing Withstands Impact
- Several Can be Stacked Horizontally or Vertically
Red Lion C48C Series User Manual
Specifications
Display
Main Display: 0.3" digits
Secondary Display: 0.2" digits
Annunciators: Value- PRS, 1, 2, & 3; Output- 01, 02, 03
Power Requirements
AC Power: 85-250 VAC, 50/60 Hz, 9 VA max
DC Power: 11-14 VDC @ 150 mA max
Memory
Nonvolatile E2PROM retains all programmable parameters and count values
Sensor Power
+12 VDC (+/- 15%) @100 mA max
Count Inputs A & B
Current Sourcing: 3.9KOhm pull-down, VIN max = 30 VDC
Current Sinking: 7.8KOhm pull-up to 12 VDC; ISNK = 1.8 mA max
Debounce: 50 Hz max
Lo Bias: VIL = 1.5 VDC max., VIH = 3.75 VDC min.
Hi Bias: VIL = 5.5 VDC max., VIH = 7.5 VDC min
User Inputs
Current Sinking: VIL = 1.5 VDC max, 22 KOhm pull-up to 5 VDC
Current Sourcing: VIH = 3.5 VDC min., VIN max = 30 VDC; 22 KOhm pulldown
Response Time: 10 msec max.
Inhibit Response Time: 250 usec max.
Outputs
Solid State: NPN Open Collector- ISNK = 100 mA max. @ VOL = 1.1 VDC max.; VOH = 30 VDC max.
Standards Compliance
UL & CUL Recognized
Electrostatic Discharge: EN 61000-4-2
Electromagnetic RF Fields: EN 61000-4-3
Fast Transients (burst): EN 61000-4-4
RF Conducted Interference: EN 61000-4-6
Simulation of Cordless Phone: ENV 50204
RF Interference: EN 55011
Physical
Operating Temperature: 0 C to 50 C (32 F to 122 F)
Storage Temperature: -40 C to 70 C (-40 F to 158 F)
Humidity: 85% max. relative humidity (non-condensing) from 0 C to 50 C.
Altitude: Up to 2000 meters
Housing: Black Plastic
Electrical Connection: Wire clamping screw terminals
Dimensions: 1.95" x 1.95" x 4.54"
RS-485 Serial Communications
Baud Rate: Programmable from 1200 to 9600 baud
Address: Programmable from 0 to 99
Data Format: 10 Bit Frame, 1 start bit, 7 or 8 data bits, 1 or No Parity bit, & 1 stop bit
Parity: Programmable for Odd (7 data bits), Even (7 data bits), or None (8 data bits)
Red Lion Panel Meter