Home > Panel Meters > PAX 1/8 DIN Intelligent Panel Meters >

Red Lion PAXTM000 Timer Panel Meter, 6 Digit, Red LED, AC

Red Lion Timer, 6 Digit, Red LED, AC
Red Lion PAXTM000 Timer Panel Meter, 6 Digit, Red LED, AC


 
Alternative Views:


Price: $262.00
Note: Call 800-966-2345 for Lead Time
MFG P/N: PAXTM000
MFG: Red Lion
Weight (lbs): 0.65



Availability:
In Stock
Product Code: PAXTM000
Qty:

Description
 

The Red Lion PAXTM000 PAX series timer panel meter can be used as an elapsed or preset timer. It has a 6 digit, red LED display in a 1/8 DIN housing. There are two inputs with 23 timing ranges, with the ability to be a dual or quad output timer with an option card. It features communication and bus capabilities through option cards, including RS232, RS485, Modbus, DeviceNet, and Profibus-DP. There are 5 function keys on the front, with 3 being programmable to meet the needs of the application. Four setpoint outputs are possible through with an optional digital output card. AC powered .

Features

  • 1/8 DIN Housing
  • 6 Digit, Red LED Display
  • Elapsed Timer w/Preset Capability
  • Counter w/Preset Capability
  • Cycle Counting Capability
  • Programmable Function Keys/User Inputs
  • 4 Setpoint Alarm Outputs (w/Option card)
  • Communication & Bus Capability (w/Option card)
  • Crimson Programming Software
  • 85 to 250 VAC Input Power
  • NEMA 4X/IP65 - Front Panel
  • Can Switch Between Parameter Lists
  • Inputs Can be Switch Contacts, CMOS & TTL Circuit Outputs
  • Parameters Can be Completely or Partially Locked After Setup
  • Not made to directly command motors, valves or actuators without safeguards

Red Lion PAX Series Timer User Manual

Specifications

Display
6 digit, 0.56" (14.2 mm) red sunlight readable LED
Annunciators:
TMR- Timer, CNT- Cycle Counter
SP1 - setpoint 1 output state, SP2 - setpoint 2 output state, SP3 - setpoint 3 output state, SP4 - setpoint 4 output state
Power Requirements
AC Power: 85 to 250 VAC, 50/60 Hz, 18 VA
Isolation: 2300 Vrms for 1 min. to all inputs and outputs.
Sensor Power
12 VDC, +/-10%, 100 mA max. Short circuit protected
Memory
Nonvolatile E2PROM retains programmable parameters & display values
User Inputs
Three programmable user inputs
Logic inputs configurable as Current Sinking (active low) or Current
Sourcing (active high) through a single plug jumper.
Current Sinking (active low): VIL = 0.9 V max., 22 KOhm pull-up to +12 VDC.
Current Sourcing (active high): VIH = 3.6 V min., 22 KOhm pull-down, Max.
Continuous Input: 30 VDC.
Isolation To Timer Input Common: Not isolated
Response Time: 10 msec
Timer Display
Timer Range: 23 Selectable Ranges
Timing Accuracy: +/- 0.01%
Minimum Digit Resolution: 0.001 Sec.
Maximum Least Significant Digit Resolution: 1 Hr.
Maximum Display: 999999
Cycle Counter Display
Counter Range: 0 to 999999
Digit Resolution: 1 cycle
Maximum Count Rate: 50 Hz
Timer Inputs A & B
Logic inputs configurable as Current Sinking (active low) or Current
Sourcing (active high) via a single plug jumper.
Current Sinking (active low): VIL = 0.9 V max., 22 KOhm pull-up to +12 VDC.
Current Sourcing (active high): VIH = 3.6 V min., 22 KOhm pull-down, Max.
Continuous Input: 30 VDC.
Timer Input Pulse Width: 1 msec min.
Timer Start/Stop Response Time: 1 msec max.
Filter: Software filtering provided for switch contact debounce. Filter
enabled or disabled through programming.
If enabled, filter results in 50 msec start/stop response time for successive
pulses on the same input terminal
Standards Compliance
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
EN 61010-1: General Requirements
EN 61010-2-030: Particular Requirements for Testing and Measuring Circuits
RoHS Compliant
UL Recognized Component: File #E179259
UL Listed: File #E137808
Type 4X Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)
Physical
Operating Temperature: 0 C to 50 C (32 F to 122 F)
Storage Temperature: -40 C to 60 C (-40 F to 140 F)
Humidity: 85% max. relative humidity (non-condensing)
Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.
Shock to IEC 68-2-27: Operational 25 g (10 g relay).
Altitude: Up to 2000 meters
Construction: NEMA 4X/IP65 outdoor use, IP20 Touch Safe, Installation Category II,
Pollution Degree 2, One piece bezel/case; flame resistant; Synthetic rubber keypad; panel gasket & mounting clip
Connection: High Compression Cage-Clamp Terminal Block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
Dimensions: 1.95" x 3.8" x 4.2"

PAXTM000 Timer Panel Meter with 1/8 DIN Housing

Additional Product Information

Panel Meter Comparison Chart