The Legrand HBP-112-L7 passive infrared occupancy sensor is compatible with SLG high bay luminaires. Works with 120/230/277/347V AC single phase operation. This sensor can accommodate up to a 100 ft diameter at a 40 ft height. Can be mounted from 15-40 feet). A daylight Light Level feature can keep the light off when there is sufficient ambient light. An included accessory can mask the lens for aisleway lighting. This sensor mounts directly to the fixture. The time delay sets the amount of time the light stays on once motion is no longer detected.
- 120, 277, 347V, 60Hz or 230V, single phase, 50Hz operation
- 360 degree coverage unless set for aisleway lighting
- Adjustable time delay (5-30 min, default 15 min)
- Adjustable light level (1-300 footcandles, default 300 footcandles)
- Multi-cell, multi-tier Fresnel lens
- UL Listed snap-on mounting hardware
- RoHS compliant
- Ideal for use in gymasiums, warehouses, and distribution centers
- 4.95" H x 2.76" W x 1.64" D
- Operating Temperature: 32-158 F (0-70 C)
- Humidity: 5-95%, non condensing
- For inside use only
- ABS plastic housing
- 5 year manufacturer's warranty
- Load ratings:
- 120VAC, 60Hz: 0-1000VA, 1/4hp
- 230VAC, 50/60Hz: 0-1000VA
- 277VAC, 60Hz: 0-1200VA, 1/4hp
- 347VAC, 60Hz: 0-1500VA, 1/4hp
Legrand Occupancy Sensor Installation Instructions
High Bay/Low Bay Passive Infrared Occupancy Sensor
|
|
|
|
|
|
|