The Red Lion C48CD110 C48 series panel meter is a standard dual preset counter with dual NPN OC outputs. It has a 2 line, 6 digit, transmissive LCD display with backlighting and a 1/16 DIN housing. The backlit display features a red digital readout on the main line and a green readout on the lower line. The noise interference resistance makes it perfect for industrial environments. DC powered.

Features

  • Two Presets
  • Bi-directional & Quadrature Counting
  • Dual Line, 6 Digit Transmissive LCD Display w/Backlighting
  • Red Top Line & Green Lower Line
  • Dual NPN OC Outputs
  • Up to 11KHz
  • NEMA 4X/IP65 - Front Panel
  • Status Indicators for Outputs
  • Programmable User Inputs
  • Function Keys on Front Panel
  • Lightweight Housing Withstands Impact
  • Can be Stacked Horizontally or Vertically

Red Lion C48C Series User Manual

Specifications

Display
Main Display: 0.3" digits
Secondary Display: 0.2" digits
Annunciators: Value- PRS, 1, 2, & 3; Output- 01, 02, 03
Power Requirements
DC Power: 18-36 VDC, 5.5 W max.
AC Power: 24 VAC +/- 10%; 50/60 Hz; 7 VA max.
Memory
Nonvolatile E2PROM retains all programmable parameters and count values
Sensor Power
+12 VDC (+/- 15%) @100 mA max
Count Inputs A & B
Current Sourcing: 3.9KOhm pull-down, VIN max = 30 VDC
Current Sinking: 7.8KOhm pull-up to 12 VDC; ISNK = 1.8 mA max
Debounce: 50 Hz max
Lo Bias: VIL = 1.5 VDC max., VIH = 3.75 VDC min.
Hi Bias: VIL = 5.5 VDC max., VIH = 7.5 VDC min
User Inputs
Current Sinking: VIL = 1.5 VDC max, 22 KOhm pull-up to 5 VDC
Current Sourcing: VIH = 3.5 VDC min., VIN max = 30 VDC; 22 KOhm pulldown
Response Time: 10 msec max.
Inhibit Response Time: 250 usec max.
Outputs
Solid State: NPN Open Collector- ISNK = 100 mA max. @ VOL = 1.1 VDC max.; VOH = 30 VDC max.
Standards Compliance
UL & CUL Recognized
Electrostatic Discharge: EN 61000-4-2
Electromagnetic RF Fields: EN 61000-4-3
Fast Transients (burst): EN 61000-4-4
RF Conducted Interference: EN 61000-4-6
Simulation of Cordless Phone: ENV 50204
RF Interference: EN 55011
Physical
Operating Temperature: 0 C to 50 C (32 F to 122 F)
Storage Temperature: -40 C to 70 C (-40 F to 158 F)
Humidity: 85% max. relative humidity (non-condensing) from 0 C to 50 C.
Altitude: Up to 2000 meters
Housing: Black Plastic
Electrical Connection: Wire clamping screw terminals
Dimensions: 1.95" x 1.95" x 4.54"

Red Lion C48 Series Panel Meter

Additional Product Information

The panel meter has nine programmable counting modes, and can be programmed to register counts on both edges of the input signal. Programming modes & data values, changing the display, and resetting is done through the function keys located on the front. Data entry is achieved through digit entry or automatic scrolling. User inputs can be sinking (active low) or sourcing (active high) through a single plug jumper. The NPN open collector solid state outputs are activated through presets 1 and 2.

Panel Meter Comparison Chart