Network size - Length of cable
|
Singlemode fiber (SM) 9/125 µm
|
0 - 32.5 km, 16 dB link budget at 1300 nm, A = 0.4 dB/km, 3 dB reserve, D = 3.5 ps/(nm x km)
|
Power requirements
|
Operating voltage
|
Power supply via the backplane of the MICE switch
|
Power consumption
|
5W
|
Service
|
Diagnostics
|
LEDs (power, link status, data, 100 Mbit/s, full duplex, ring port, LED test)
|
Ambient conditions
|
Standard operating temperature
|
0 C to +60 C
|
Storage/transport temperature
|
-40 C to +70 C
|
Protective paint on PCB
|
optional
|
Relative humidity (non-condensing)
|
10% to 95%
|
MTBF
|
67 years; MIL-HDBK 217F: Gb 25 C
|
Mechanical construction
|
Dimensions (W x H x D)
|
38 mm x 134 mm x 77 mm
|
Mounting
|
Backplane
|
Weight
|
170 g
|
Protection class
|
IP 20
|
Mechanical stability
|
IEC 60068-2-27 shock
|
15 g, 11 ms duration, 18 shocks
|
IEC 60068-2-6 vibration
|
1 mm, 2 Hz - 13.2 Hz, 90 min.; 0.7g, 13.2 Hz - 100 Hz, 90 min.; 3.5 mm, 3 Hz - 9 Hz, 10 cycles, 1 octave/min.; 1g, 9 Hz - 150 Hz, 10 cycles, 1 octave/min
|
EMC interference immunity
|
EN 61000-4-2 electrostatic discharge (ESD)
|
6 kV contact discharge, 8 kV air discharge
|
EN 61000-4-3 electromagnetic field
|
10 V/m (80 - 1000 MHz)
|
EN 61000-4-4 fast transients (burst)
|
2 kV power line, 1 kV data line
|
EN 61000-4-5 surge voltage
|
power line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line
|
EN 61000-4-6 conducted immunity
|
3 V (10 kHz - 150 kHz), 10 V (150 kHz - 80 MHz)
|
EMC emitted immunity
|
FCC CFR47 Part 15
|
FCC CFR47 Part 15 Class A
|
EN 55022
|
EN 55022 Class A
|
Approvals
|
Safety of industrial control equipment
|
cUL 508
|
Hazardous locations
|
ISA 12.12.01 Class 1 Div. 2
|
Shipbuilding
|
Germanischer Lloyd
|
Scope of delivery and accessories
|
Scope of delivery
|
module, operating manual
|
Accessories to order separately
|
ML-MS2/MM labels
|